K. MACHINE PROTECT LIMIT FAULTS
Excessive numbers of the same fault can lead to severe
machine damage. Seek service expertise.
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
PROTECTIVE LIMIT HIGH DISCHARGE TEMP CMPD VALUE exceeded
limit of [LIMIT]*. Check oil
temperature.
Check discharge temperature immediately. Check
for sensor accuracy. Check for proper con-
denser flow and temperature, check oil sump tem-
perature. Check condenser for fouled tubes or
air in machine.
PROTECTIVE LIMIT LOW REFRIGERANT TEMP ERT VALUE exceeded limit of
[LIMIT]*. Check evap pump and
flow switch.
Check for proper amount of refrigerant charge,
check for proper water flow and temperatures.
Check for proper slide valve operation.
PROTECTIVE LIMIT HIGH MOTOR TEMPERATURE MTRW VALUE exceeded limit
of [LIMIT]*. Check motor
cooling.
Check motor temperature immediately. Check sen-
sor for accuracy. Check for proper condenser flow
and temperature. Check motor cooling system
for restrictions. Check refrigerant filter.
PROTECTIVE LIMIT OIL LEVEL SENSOR OILSS check oil level in sepa-
rator.
Check for low oil level. Check oil level switch op-
eration.
PROTECTIVE LIMIT LOW OIL PRESSURE OILPD VALUE exceeded limit
of [LIMIT]*. Check oil system, oil
solenoid, and transducer.
Check oil level, check for dirty filter. Check tower
water temperature.
PROTECTIVE LIMIT NO MOTOR CURRENT CA P Loss of Motor Current:
Check sensor and signal.
Check wiring: Check torque setting on solid state
starter. Check for main circuit breaker trip. Check
power supply to PSIO module.
PROTECTIVE LIMIT POWER LOSS V P Power Loss: Check volt-
age supply.
Check 24-vdc input sensor on the SMM; adjust
potentiometer if necessary. Check transformers
to SMM. Check distribution bus. Consult power
company.
PROTECTIVE LIMIT LOW LINE VOLTAGE V P VALUE exceeded limit of
[LIMIT]*. Check voltage
supply.
PROTECTIVE LIMIT HIGH LINE VOLTAGE V P VALUE exceeded limit
of [LIMIT]*. Check voltage
supply.
PROTECTIVE LIMIT LOW CHILLED WATER FLOW EVFL Flow Fault: Check evap.
pump/flow switch.
Perform pumps control test and verify proper switch
operation. Check all water valves and pump op-
eration.
PROTECTIVE LIMIT LOW CONDENSER WATER FLOW CDFL Flow Fault: Check cond.
pump/flow switch.
PROTECTIVE LIMIT HIGH CONDENSER PRESSURE PRS TRIP High Condenser
Pressure: Check switch and
water temp/flow.
Condenser pressure transducer tripped ma-
chine. Check for proper condenser water flows
and temperature. Check high-pressure switch.
PROTECTIVE LIMIT HIGH CONDENSER PRESSURE CRP VALUE exceeded limit
of [LIMIT]*. Check condenser
water and transducer.
Check discharge pressure switch. Check for proper
condenser flow and temperature. Check for fouled
tubes.
PROTECTIVE LIMIT 1CR AUX CONTACT FAULT CR AUXStarter Contact Fault:
Check 1CR/1M aux contacts.
1CR auxiliary contact opened while machine was
running. Check starter for proper operation.
PROTECTIVE LIMIT RUN AUX CONTACT FAULT RUN AUX Starter Contact
Fault: Check 1CR/1M aux
contacts.
Run auxiliary contact opened while machine was
running. Check starter for proper operation.
PROTECTIVE LIMIT CCN OVERRIDE STOP CHIL S S CCN Override
Stop while in LOCAL run mode.
CCN has signaled machine to stop. Reset and
restart when ready. If the signal was sent by the
LID, release the Stop signal on STATUS01 screen.
PROTECTIVE LIMIT SPARE SAFETY DEVICE SRP PL Spare Safety Fault:
Check contacts.
Spare safety input has tripped or factory-installed
jumper not present.
PROTECTIVE LIMIT EXCESSIVE MOTOR AMPS CA P VALUE exceeded limit
of [LIMIT]*. High Amps; Check
slide valve.
Check motor current for proper calibration. Check
slide valve for proper operation.
PROTECTIVE LIMIT STARTER FAULT STR FLT Starter Fault: Check
starter for fault source.
Check starter for possible ground fault, reverse
rotation, voltage trip, etc.
PROTECTIVE LIMIT STARTER OVERLOAD TRIP STR FLT Starter Overload
Trip: Check amps calibration/
reset overload.
Reset overloads and reset alarm. Check motor
current calibration or overload calibration (do not
field-calibrate overloads).
PROTECTIVE LIMIT TRANSDUCER VOLTAGE FAULT V REF VALUE exceeded limit
of [LIMIT]*. Check transducer
power supply.
Check transformer power (5 vdc) supply to
transducers. Power must be 4.5 to 5.5 vdc.
PROTECTIVE LIMIT DIRTY OIL FILTER OILP exceeded limit of [LIMIT]*.
Replace oil filter.
Check oil filter. Check solenoid valve operation.
Check oil supply valves. Check discharge and
oil transducer accuracy.
PROTECTIVE UNIT† LOW DISCHARGE SUPERHEAT Lowdischarge superheat. Check
refrigerant and oil charges.
Excessive oil/refrigerant charge, low load opera-
tion. Reclaim oil lost to refrigerant circuit; re-
move excess oil. Do not operate machine below
minimum load. Check tower control operation.
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert.
†Applicable to Frame 1 and 2 units only.