EXAMPLE3—STATUS03 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
.
3. Scroll down to highlight STATUS03.
4. Press SELECT .
DESCRIPTION RANGE UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
OPTIONS BOARD 1
*Demand Limit 4-20 mA 4-20 MA DEM OPT
*Temp Reset 4-20 mA 4-20 MA RES OPT
*Common CHWS Sensor −40-245 (−40-118) DEG F (DEG C) CHWS
*Common CHWR Sensor −40-245 (−40-118) DEG F (DEG C) CHWR
*Remote Reset Sensor −40-245 (−40-118) DEG F (DEG C) R RESET
*Temp Sensor — Spare 1 −40-245 (−40-118) DEG F (DEG C) SPARE1
*Temp Sensor — Spare 2 −40-245 (−40-118) DEG F (DEG C) SPARE2
*Temp Sensor — Spare 3 −40-245 (−40-118) DEG F (DEG C) SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 1 4-20 MA SPARE1 M
*4-20 mA — Spare 2 4-20 MA SPARE2 M
*Temp Sensor — Spare 4 −40-245 (−40-118) DEG F (DEG C) SPARE4
*Temp Sensor — Spare 5 −40-245 (−40-118) DEG F (DEG C) SPARE5
*Temp Sensor — Spare 6 −40-245 (−40-118) DEG F (DEG C) SPARE6
*Temp Sensor — Spare 7 −40-245 (−40-118) DEG F (DEG C) SPARE7
*Temp Sensor — Spare 8 −40-245 (−40-118) DEG F (DEG C) SPARE8
*Temp Sensor — Spare 9 −40-245 (−40-118) DEG F (DEG C) SPARE9
EXAMPLE 4 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SETPOINT
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Base Demand Limit 40-100 % DLM 100
LCW Setpoint 15-120 (−9.44-48.9) DEG F (DEG C) sp LCW SP
50.0 (10.0)
ECW Setpoint 20-120 (−6.7-15.6) DEG F (DEG C) ECW SP
60.0 (15.6)
Ice Build Setpoint 20-60 (−6.7-15.6) DEG F (DEG C) ice SP
40.0 (4.4)
EXAMPLE 5 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
.
5. Scroll down to highlight CONFIG.
6. Press SELECT
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA −30-30 (−17-17) DEG F (DEG C) deg 20mA
10D)(6D))
RESET TYPE 2
Remote Temp (No Reset) −40-245 (−40-118) DEG F (DEG C) res rt1
85 (29)
Remote Temp (Full Reset) −40-245 (−40-118) DEG F (DEG C) res rt2 65 (18)
Degrees Reset −30-30 (−17-17) DEG F (DEG C) deg rt 10D (6D)
RESET TYPE 3
CHW Delta T (No Reset) 0-15 (0-8) DEG F (DEG C) restd 1
10D (6D)
CHW Delta T (Full Reset) 0-15 (0-8) DEG F (DEG C) restd 2 0D (0D)
Degrees Reset −30-30 (−17-17) DEG F (DEG C) deg chw 5D (3D)
Select/Enable Reset Type 0-3 res sel
0
ECW Control Option 0/1 DSABLE/ENABLE ecw opt
0
Demand Limit At 20 mA 40-100 % dem 20mA 40
20mA Demand Limit Option 0/1 DS/ENABLE dem sel
0
Auto Restart Option 0/1 DS/ENABLE astart 0
Remote Contacts Option 0/1 DS/ENABLE r contact
0
Temp Pulldown Deg/Min 2-10 tmp ramp
3
Load Pulldown %/Min 5-20 kw ramp 10
Select Ramp Type: 0/1 ramp opt 1
Temp=0,Load=1
Loadshed Group Number 0-99 ldsgrp 0
Loadshed Demand Delta 0-60 % ldsdelta 20
Maximum Loadshed Time 0-120 MIN maxldstm 60
CCN Occupancy Config:
Schedule Number 3-99 OCCpcxxe 3
Broadcast Option 0/1 DS/ENABLE OCCbrcst 0
Ice Build Option 0/1 DS/ENABLE ibopt DISABLE
Ice Build Termination 0-2 ibterm 0
0=Temp, 1=Contacts, 2=Both
Ice Build Recycle Option 0/1 DS/ENABLE ibrecyc DISABLE
NOTE: D = delta degrees