Carrier 23XL Spezifikationen Seite 23

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 104
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 22
The proportional band can be viewed/modified on the LID.
There are two response modes, one for temperature re-
sponse above the control point, the other for response below
the control point.
The first type is called PROPORTIONAL INC BAND and
it can slow or quicken slide valve response to chilled water/
brine temperature above DEADBAND. The PROPOR-
TIONAL INC BAND can be adjusted from a setting of 5 to
10; the default setting is 6.5. PROPORTIONAL DEC BAND
can slow or quicken slide valve response to chilled water
temperature below control point plus deadband. It can be ad-
justed on the LID from a setting of 5 to 10, and the default
setting is 6.0. Increasing either of these settings will cause
the slide valve to respond slower than a lower setting.
The PROPORTIONAL ECW GAIN can be adjusted at the LID
display for values of 1, 2, or 3, with a default setting of 2.
Increase this setting to increase slide valve response to a change
in entering cooler water temperature. The proportional bands
and gain may be viewed/modified on the Equipment Service
table, Service3 selection.
DEMAND LIMITING The PIC will respond to the AC-
TIVE DEMAND LIMIT set point by limiting the closing of
the slide valve. It will compare the set point to either COM-
PRESSOR MOTOR LOAD or COMPRESSOR MOTOR
CURRENT (percentage), depending on how the control is
configured for the DEMAND LIMIT SOURCE which is ac-
cessed on the SERVICE1 table. The default setting is cur-
rent limiting.
MACHINE TIMERS The PIC maintains 2 runtime clocks,
known as COMPRESSOR ONTIME and SERVICE ON-
TIME. COMPRESSOR ONTIME indicates the total lifetime
compressor run hours. This timer can register up to 500,000
hours before the clock turns back to zero. The SERVICE ON-
TIME is a resettable timer that can be used to indicate the
hours since the last service visit or any other reason. The
time can be changed through the LID to whatever value is
desired. This timer can register up to 32,767 hours before it
rolls over to zero.
The chiller also maintains a 15-minute start-to-start timer
and a 1-minute stop-to-start timer (PSIO Software Version
13 and higher). A 3-minute stop-to-start timer is on PSIO
Version 12 and lower. These timers limit how soon the ma-
chine can be started. See the Start-Up/Shutdown/Recycle Se-
quence section on page 37 for operational information.
OCCUPANCY SCHEDULE This schedule determines when
the chiller is either occupied or unoccupied. See Fig. 20
and 21.
PSIO Software Version 12 and Lower Whenever the chiller
is in the LOCAL mode, the machine will start when Occu-
pancy Schedule 01 indicates occupied. When in CCN mode,
Occupancy Schedule 02 is used. The machine will shut down
when the schedule goes to UNOCCUPIED. The schedule
can be set up to follow the building schedule or to be 100%
OCCUPIED if the operator wishes the machine to start when-
ever the PIC is in LOCAL mode. The schedule also can be
bypassed by forcing the Start/Stop command on the PIC sta-
tus screen to start. The schedule also can be overridden to
keep the unit in an OCCUPIED mode for up to 4 hours, on
a one-time basis.
PSIO Software Version 13 and Higher The Local Time
Schedule is Schedule 01. The Ice Build Time Schedule is
Schedule 02 and the CCN Default Time Schedule is Sched-
ule 03. The CCN schedule number is defined on the Config
table in the Equipment Configuration table on page 25. The
schedule number can change to any value from 03 to 99. If
this schedule number is changed on the Config table, the op-
erator must use the Attach to Network Device table
to upload the new number into the schedule screen. See
Fig. 21.
Each schedule consists of from one to 8 occupied/unoccupied
time periods, set by the operator. These time periods can be
enabled to be in effect (or not in effect) on each day of the
week and for holidays. The day begins with 0000 hours and
ends with 2400 hours. The machine is in OCCUPIED mode
unless an unoccupied time period is in effect.
Figure 22 shows a typical office building time schedule,
with a 3-hour, off-peak cool down period from midnight to
3 a.m., following a weekend shutdown. Example: Holiday
periods are unoccupied 24 hours per day. The building op-
erates Monday through Friday, 7:00 a.m. to 6:00 p.m., with
a Saturday schedule of 6:00 a.m. to 1:00 p.m., and includes
the Monday midnight to 3:00 a.m. weekend cool-down
schedule.
NOTE: This schedule is for illustration only and is not in-
tended to be a recommended schedule for chiller operation.
Safety Controls The PIC monitors all safety control
inputs, and, if required, shuts down the machine, or limits
the slide valve to protect it from possible damage from any
of the following conditions:
high motor winding temperature
high discharge temperature
low discharge superheat temperature (Frame 1 and 2
machines)
low oil pressure
high oil filter pressure drop
low oil level
low cooler refrigerant temperature
condenser high pressure
inadequate water/brine cooler and condenser flow
high, low, or loss of voltage
excessive motor acceleration time
excessive starter transition time
lack of motor current signal
excessive motor amps
motor power supply phase reversal
temperature sensor and transducer faults
Starter faults or optional protective devices within the starter
can shut down the machine. These devices are dependent on
what has been purchased as options.
If compressor motor overload occurs, check the motor
for grounded or open phases before attempting a
restart.
If the controller initiates a safety shutdown, it displays the
fault on the LID display with a primary and a secondary mes-
sage. It also energizes an alarm relay in the starter and blinks
the alarm light on the control center. The alarm is stored in
memory and can be viewed in the PIC alarm table along with
a message for troubleshooting.
To give more specific operating condition warning, the op-
erator also can define alert limits on various monitored in-
puts. Safety contact and alert limits are defined in Table 4.
Alarm and alert messages are listed in the Troubleshooting
Guide section, page 68.
SHUNT TRIP The shunt trip function of the PIC is a safety
trip. The shunt trip is wired from an output on the SMM to
the motor circuit breaker. If the PIC tries to shutdown the
compressor through normal shutdown procedure but is un-
successful for 30 seconds, the shunt trip output is energized
and causes the circuit breaker to trip off. If ground fault pro-
tection has been applied to the starter, the ground fault trip
will also energize the shunt trip to trip the circuit breaker.
23
Seitenansicht 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 103 104

Kommentare zu diesen Handbüchern

Keine Kommentare