
Water/Brine Reset — Three types of chilled water or
brine reset are available and can be viewed or modified on
the Equipment Configuration menu Config table.
The default screen status message indicates when the chilled
water reset is active. The CONTROL POINT, on the
Status01 table, indicates the machine’s reset temperature.
To activate a reset type, input all configuration informa-
tion for that reset type in the Config table. Then input the
reset type number in the DISABLE/ENABLE input line.
1. Reset Type 1 (Requires optional 8-input module) — Au-
tomatic chilled water temperature reset based ona4to
20 mA input signal. This type permits up to ±30° F
(±16° C) of automatic reset to the chilled water or brine
temperature set point, based on the input froma4to
20 mA signal. This signal is hardwired into the number
one 8-input module.
If the 4 to 20 mA signal is externally powered from the
8-input module, the signal is wired to terminals J1-5(+)
and J1-6(−). If the signal is to be internally powered by
the 8-input module (for example, when using variable re-
sistance), the signal is wired to J1-7(+) and J1-6(−). The
PIC must now be configured on the Service2 table to en-
sure that the appropriate power source is identified.
2. Reset Type 2 (Requires optional 8-input module) — Au-
tomatic chilled water temperature reset based on a
remote temperature sensor input. This type permits
±30° F (±16° C) of automatic reset to the set point based
on a temperature sensor wired to the number one 8-input
module (see wiring diagrams or certified drawings).
The temperature sensor must be wired to terminal J1-19
and J1-20.
To configure Reset Type 2, enter the temperature of the
remote sensor at the point where no temperature reset will
occur. Next, enter the temperature at which the full amount
of reset will occur. Then, enter the maximum amount of
reset required to operate the machine. Reset Type 2 can
now be activated.
3. Reset Type 3 — Automatic chilled water temperature re-
set based on cooler temperature difference. This type of
reset will add ±30° F (±16° C) based on the temperature
difference between entering and leaving chilled water tem-
perature. This is the only type of reset available without
the need of the number one 8-input module. No wiring is
required for this type as it already uses the cooler water
sensors.
To configure Reset Type 3, enter the chilled water tem-
perature difference (the difference between entering and
leaving chilled water) at which no temperature reset oc-
curs. This chilled water temperature difference is usually
the full design load temperature difference. The differ-
ence in chilled water temperature at which the full amount
of reset will occur is now entered on the next input line.
Next, the amount of reset is entered. Reset Type 3 can
now be activated.
Demand Limit Control, Option — (Requires Op-
tional 8-Input Module) —
The demand limit may be
externally controlled witha4to20mAsignal from an en-
ergy management system (EMS). The option is set up on the
Config table. When enabled, the control is set for 100% de-
mand with 4 mA and an operator configured minimum de-
mand set point at 20 mA.
The Demand Reset input from an energy management sys-
tem is hardwired into the number one, 8-input module. The
signal may be internally powered by the module or exter-
nally powered. If the signal is externally powered, the
signal is wired to terminals J1-1(+) and J1-2(−). If the signal
is internally powered, the signal is wired to terminals J1-
3(+) and J1-2(−).
Hot Gas Bypass (Optional) Algorithm (See
Fig. 24 and 25) —
If a hot gas bypass solenoid valve is
present, and the hot gas bypass option on the SERVICE1
table is enabled, this operator configurable feature can de-
termine if load conditions are too low for the compressor
and then take corrective action.
The algorithm first determines if corrective action is nec-
essary. This is done by checking two sets of operator con-
figured data points, which are the MINIMUM and the
MAXIMUM Load Points, (T1/P1;T2/P2). These points have
default settings for each type of refrigerant, HCFC-22 or HFC-
134a, as defined on the SERVICE1 table, and on Table 3.
These settings and the algorithm logic are graphically dis-
played in Fig. 24 and 25. The two sets of load points on this
graph (default settings are shown) describe a line which the
algorithm uses to activate the hot gas bypass. Whenever the
temperature difference between the entering and leaving chilled
water is on the left side of the line on the graph (as defined
by the MINIMUM and MAXIMUM Load Points), the al-
gorithm will then energize the hot gas bypass valve to falsely
load the machine and prevent displacement of oil. If the ac-
tual values are on the right side of the line, the algorithm
takes no action.
LEGEND
DP—Condenser Pressure-
Cooler Pressure
DT—ECW-LCW
ECW — Entering Chilled
Water Temperature
LCW — Leaving Chilled
Water Temperature
HGBP — Hot Gas Bypass
DEFAULT VALUES:
POINT HCFC-22 HFC-134a
DT
1
2.5 2.5
DP
1
50 30
DT
2
10 10
DP
2
200 170
Fig. 24 — 23XL Hot Gas Bypass (English)
LEGEND
DP—Condenser Pressure-
Cooler Pressure
DT—ECW-LCW
ECW — Entering Chilled
Water Temperature
LCW — Leaving Chilled
Water Temperature
HGBP — Hot Gas Bypass
DEFAULT VALUES:
POINT HCFC-22 HFC-134a
DT
1
1.4 1.4
DP
1
345 207
DT
2
5.6 5.6
DP
2
1379 1172
Fig. 25 — 23XL Hot Gas Bypass (SI)
32
Kommentare zu diesen Handbüchern