Carrier 23XL Spezifikationen Seite 21

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 104
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 20
For Discrete Points Press START or STOP to se-
lect the desired state.
For Analog Points Press INCREASE or
DECREASE
to select the desired value.
3. Press ENTER to register new value.
NOTE: When overriding or changing metric values, it is nec-
essary to hold the softkey down for a few seconds in order
to see a value change, especially on kilopascal values.
To Remove an Override
1. On the Point Status table press NEXT or
PREVIOUS
to highlight the desired point.
2. Press SELECT to access the highlighted point.
3. Press RELEASE to remove the override and return the
point to the PIC’s automatic control.
Override Indication An override value is indicated by
‘SUPVSR’’, ‘SERVC’’, or ‘BEST’flashing next to the point
value on the Status table.
TIME SCHEDULE OPERATION (Fig. 22)
1. On the Menu screen, press SCHEDULE
.
2. Press NEXT or PREVIOUS to highlight the de-
sired schedule. When using PSIO Software Version 8 or
12, OCCPC01S is the LOCAL Time Schedule and
OCCPC02S is the CCN Time Schedule. When using PSIO
Software Version 13 and higher, OCCPC01S is the LO-
CAL Time Schedule, OCCPC02S is the Ice Build Time
Schedule, and OCCPC03S is the CCN Time Schedule
(the actual CCN Occupied Schedule number is defined
on the Config table). The schedule number can change
to any value from 03 to 99.
3. Press SELECT to access and view the time schedule.
4. Press NEXT or PREVIOUS to highlight the de-
sired period or override that you wish to change.
5. Press SELECT to access the highlighted period or
override.
6. a. Press INCREASE or DECREASE to change the
time values. Override values are in one-hour incre-
ments, up to 4 hours.
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE
to eliminate days from the
period.
7. Press ENTER to register the values and to move
horizontally (left to right) within a period.
8. Press EXIT to leave the period or override.
Fig. 22 Example of Time Schedule