Fig. 3 — Unit Label Diagram — 06D,07D Units
AUX
Auxiliary
C—
Compressor Contactor
CH
Crankcase Heater
CR
Control Relay
DX
Direct Expansion
EQUIP
Equipment
FU
Fuse
GND
Ground
HPS
High-Pressure Switch
IP
Internal Protector
LLS
Liquid Line Solenoid Valve
LPS
Low-Pressure Switch
M3
Cooling Tower Fan
NEC
National Electrical Code
OL
Overload
OPS
Oil-Pressure Switch
POR
Pumpout Relay
SW
Start-Stop-Reset Switch
LEGEND
TB
Terminal Block
TM
Timer Motor
TR
Timer Relay
Terminal Block Connector
Unmarked Terminal
Marked Terminal
Factory Wiring
Field Control Wiring
To indicate common potential only;
not to represent wiring.
Splice
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications
or additions must be in compliance with all applicable codes. Use
copper, copper-clad aluminum for field power supply only.
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are pro-
tected against primary single-phasing condition.
4. Pilot duty control must be field supplied. Minimum contact rating
must be 25 va.
5. 60 Hz units have 120-volt control circuit. 50 Hz units have
230-volt control circuit. A separate source of supply at the correct
voltage must be field supplied through a fused disconnect device
with a maximum rating of 15 A to TB2 connections
(Hot Side) and (Neutral).
6. Open control circuit disconnect switch for servicing only. Discon-
nect must remain closed for crankcase heater to operate.
7. A transformer of the following rating may be field supplied for
60 Hz units: 350 va.
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must
be replaced with 90 C wire or its equivalent.
L1