Compressor Unit Connections
— Extend power leads from
control center (contactor terminals) to compressor terminal box
and make connections as shown in Fig. 4.
Terminals 8 and 9 on motor terminal plate are for internal
protector connections. As shown in Fig. 4, run a wire from ter-
minal 9 to terminal 6 on TB2 in control center and a wire from
terminal 1 on OL2 to terminal 2 on HPS in control center.
Run crankcase heater power wiring into control center.
Connect leads to terminal 5 on pumpout relay and terminal 3
on terminal block TB2. See Fig. 5.
Affix power warning label supplied in the installers packet
to fused disconnect which energizes crankcase heater (see unit
label diagram).
CONTROL WIRING Control circuit power is 115 volts,
energized from an external source or from unit voltage through
field-supplied transformer. Transformer size required is 350 va
for 60 Hz units. External control power source must be
supplied through a 15-amp fused disconnect. Connect control
circuit power leads to terminal block TB2, terminals L1 and
L2. Terminal L2 is neutral potential (ground).
Compressor Protection
— The 06D and 07D units are factory
wired for single-pumpout control. Field addition and wiring of
line voltage remote control and liquid line solenoid valve is
required. (See unit Fig. 3 and Fig. 6.) Remote control minimum
contact rating must be 25 va. Solenoid valve must have a
maximum load rating of 50 va holding; 200 va inrush. For
applications with cooling tower, air-cooled or evaporative
condensers, add necessary auxiliary contacts in line between
compressor contactor and terminal A1 on timer. Insert desired
interlocks and overloads between terminals 5 and 9 on terminal
block TB2.
Control wiring may be modified as shown in Fig. 6 for
automatic pumpdown control; remove low-pressure switch
between timer relay and terminal 4 on TB2. Wire low-pressure
switch between terminals 9 and 6 on TB2. Add necessary
auxiliary contacts between compressor contactor and terminal
A1 on timer. Remove wire between terminal 6 on TB2 and
terminal 3 on pumpout relay. Insert required interlocks and
overloads between terminals 5 and 9 on TB2.
Limitations —
Do not use automatic pumpdown control
on direct expansion cooler applications or when compressors
are equipped with pressure-type unloader valves. Pressure
unloader valves have built-in high to low passage which allows
compressor to cycle with automatic pumpdown.
LEGEND
Fig. 4 — Compressor Terminal Diagram
HPS
High-Pressure Switch
OL
Overload Relay
TB
Terminal Block
Factory Wiring
Fig. 5 — 06D/07D Control Box Components and Connections (3-Phase)
LEGEND
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications or
additions must be in compliance with all applicable codes. Use copper,
copper-clad aluminum for field power supply only.
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected
against primary single-phasing condition.
4. Pilot duty control must be field supplied. Minimum contact rating must
be 25 va.
5. 60 Hz units have 120-volt control circuit. 50 Hz units have 230-volt con-
trol circuit. A separate source of supply at the correct voltage must be
field supplied thru a fused disconnect device with a max rating of 15 A
to TB2 connections (Hot Side) and (Neutral).
6. Open control circuit disconnect switch for servicing only. Disconnect
must remain closed for crankcase heater to operate.
7. A transformer of the following rating may be field supplied for 60 Hz
units: 350 va.
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must be
replaced with 90 C wire or its equivalent.
C—
Contactor, Compressor
NEC
National Electrical Code
CH
Crankcase Heater
OL
Overload Relay
CR
Control Relay
OPS
Oil Pressure Switch
FU
Fuse
POR
Pumpout Relay
GND
Ground Connection
SW
Switch
HPS
High-Pressure Switch
TB
Terminal Block
IP
Internal Protector
TM
Timer Motor
LPS
Low-Pressure Switch
TR
Timer Relay
L1
L2