54
Table 31 — Alarm and Alert Codes
ALARM/
ALERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM
GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
T051
Alert Circuit A, Compressor 1
Failure
Compressor feedback sig-
nal does not match relay
state
Circuit A shut down. Manual High-pressure or loss-of-
charge switch open, faulty
control relay or CPCS
board, loss of condenser
air, liquid valve closed.
T052
Alert Circuit A, Compressor 2
Failure
Compressor feedback sig-
nal does not match relay
state
Circuit A shut down. Circuit
restarted in 1 minute.
Compressor A2 not used
until alarm is reset.
Manual High-pressure switch
open, faulty control relay or
CPCS board, loss of con-
denser air, liquid valve
closed.
T053
Alert Circuit A, Compressor 3
Failure
Compressor feedback sig-
nal does not match relay
state
Circuit A shut down. Circuit
restarted in 1 minute.
Compressor A3 not used
until alarm is reset.
Manual High-pressure switch
open, faulty control relay or
CPCS board, loss of con-
denser air, liquid valve
closed.
T054
Alert Circuit A, Compressor 4
Failure
Compressor feedback sig-
nal does not match relay
state
Circuit A shut down. Circuit
restarted in 1 minute.
Compressor A4 not used
until alarm is reset.
Manual High-pressure switch
open, faulty control relay or
CPCS board, loss of con-
denser air, liquid valve
closed.
T055
Alert Circuit B, Compressor 1
Failure
Compressor feedback sig-
nal does not match relay
state
Circuit B shut down. Manual High-pressure or loss-of-
charge switch open, faulty
control relay or CPCS
board, loss of condenser
air, liquid valve closed.
T056
Alert Circuit B, Compressor 2
Failure
Compressor feedback sig-
nal does not match relay
state
Circuit B shut down. Circuit
restarted in 1 minute.
Compressor B2 not used
until alarm is reset.
Manual High-pressure switch
open, faulty control relay or
CPCS board, loss of con-
denser air, liquid valve
closed.
T057
Alert Circuit B, Compressor 3
Failure
Compressor feedback sig-
nal does not match relay
state
Circuit B shut down. Circuit
restarted in 1 minute.
Compressor B3 not used
until alarm is reset.
Manual High-pressure switch
open, faulty control relay or
CPCS board, loss of con-
denser air, liquid valve
closed.
A060
Alarm Cooler Leaving Fluid
Thermistor Failure (T1)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Chiller shutdown after
pumpdown complete.
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
A061
Alarm Cooler Entering Fluid
Thermistor Failure (T2)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Chiller shutdown after
pumpdown complete.
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T064
Alert Circuit A Saturated Con-
densing Thermistor Failure
(T3)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Circuit A shutdown after
pumpdown complete.
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T065
Alert Circuit B Saturated Con-
densing Thermistor Fail-
ure (T4)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Circuit B shutdown after
pumpdown complete.
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T066
Alert Circuit A Saturated Suction
Thermistor Failure (T5)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Circuit A shutdown after
pumpdown complete.
(EXV only)
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T067
Alert Circuit B Saturated Suction
Thermistor Failure (T6)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Circuit B shutdown after
pumpdown complete.
(EXV only).
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T068
Alert Compressor A1 Suction
Gas Thermistor Failure
(T7)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Circuit A shutdown after
pumpdown complete.
(EXV only).
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T069
Alert Compressor B1 Suction
Gas Thermistor Failure
(T8)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Circuit B shutdown after
pumpdown complete.
(EXV only).
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T073
Alert Outside Air Thermistor
Failure (T9)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Temperature reset dis-
abled. Chiller runs under
normal control/set points.
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T074
Alert Space Temperature
Thermistor Failure (T10)
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Temperature reset dis-
abled. Chiller runs under
normal control/set points.
Automatic Thermistor failure, dam-
aged cable/wire or wiring
error.
T077
Alert Circuit A Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Saturated suction is
greater than leaving fluid
temperature for more than
5 minutes
Circuit A shutdown after
pumpdown complete.
Automatic Faulty expansion valve or
EXV board, faulty cooler
suction thermistor (T5) or
leaving fluid thermistor
(T1).
T078
Alert Circuit B Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Saturated suction is
greater than leaving fluid
temperature for more than
5 minutes
Circuit B shutdown after
pumpdown complete
Automatic Faulty expansion valve or
EXV board, faulty cooler
suction thermistor (T6) or
leaving fluid thermistor
(T1).
T079
Alert Lead/Lag Thermistor
Failure
Thermistor outside range
of –40 to 245 F (–40 to
118 C)
Lead/lag algorithm runs
using Master LWT sensor
Master is lead chiller.
Automatic Dual chiller LWT thermistor
failure, damaged cable/
wire or wiring error.