OPERATING DATA
Control Methods
SWITCH — Unit is started and stopped manually by switch-
ing the ENABLE/OFF/REMOTE CONTACT switch from
OFF to ENABLE or by external contacts with the switch in the
REMOTE position. The unit can be enabled and disabled by
this action with all control methods.
7-DAY SCHEDULE — Unit is started and stopped in accor-
dance with the schedule configured under Time Clock mode.
This schedule can be configured from the Scrolling Marquee
Display or from CCN.
OCCUPANCY — Unit is started and stopped in accordance
with the occupancy schedule accessible only from CCN.
Schedule Number in Table SCHEDOVR must be configured
to 1 to utilize the local occupancy schedule, or 65-99 to utilize
a global schedule. If the Schedule Number is set to 0 the unit
will operate in a continuous 24-hr Occupied mode.
CCN — Unit is started and stopped by communication over
the CCN bus. The CHIL_S_S point in the A_UNIT table is
provided for this purpose.
Table 5 illustrates how the control method and cooling set
point select variables direct the operation of the chiller and the
set point to which it controls. The illustration also shows the
ON/OFF state of the machine for the given combinations.
Cooling Set Point Select
SINGLE — Unit operation is based on Cooling Set Point 1
(CSP1).
DUAL SWITCH — Unit operation is based on Cooling Set
Point 1 (CSP1) when the Dual Set Point switch contacts are
open and Cooling Set Point 2 (CSP2) when they are closed.
DUAL 7 DAY — Unit operation is based on Cooling Set
Point 1 (CSP1) during the occupied mode and Cool Set Point 2
(CSP2) during the unoccupied mode as configured under Time
clock mode. Control method must be configured to 0 (Switch).
DUAL CCN OCCUPIED — Unit operation is based on
Cooling Set Point 1 (CSP1) during the Occupied mode and
Cooling Set Point 2 (CSP2) during the Unoccupied mode as
configured under the local occupancy schedule accessible only
from CCN. Schedule Number in Table SCHEDOVR must be
configured to 1. If the Schedule Number is set to 0, the unit will
operate in a continuous 24-hr Occupied mode. Control method
must be configured to 0 (switch). See Table 5.
4 TO 20 mA INPUT — Unit operation is based on an exter-
nal 4 to 20 mA signal input to the Energy Management Module
(EMM).
Ice Mode —
When Ice Mode is enabled Cooling Set Point
Select must be set to Dual Switch, Dual 7 day or Dual CCN
Occupied and the Energy Management Module (EMM) must
be installed. Unit operation is based on Cooling Set Point 1
(CSP1) during the Occupied mode, Ice Set Point (CSP3)
during the Unoccupied mode with the Ice Done contacts open
and Cooling Set Point 2 (CSP2) during the Unoccupied mode
with the Ice Done contacts closed. These 3 set points can be
utilized to develop your specific control strategy.
Chilled Water Flow Switch —
Installation of a chilled
water flow switch is recommended to prevent operation with-
out flow through the cooler. Serious damage may result. It is
also recommended that the chiller be interlocked with the chill-
er water pump starter to provide additional protection. Inputs
for a chilled water pump flow switch and/or chilled water
pump interlock are provided. See page 73 of the Field Wiring
section for proper connection of the cooler flow switch and
pump interlock. DO NOT use the chilled water flow switch to
start and stop the chiller.
Cooler Pump Control —
The 30GTN,GUN chillers
can be configured for cooler pump control.
COOLER PUMP CONTROL (CPC, Configuration Mode,
sub-mode OPT1) — Proper configuration of the cooler pump
control is required to provide reliable chiller operation. The
factory default setting for cooler pump control is “OFF”. It is
recommended for all chillers that the cooler pump control be
utilized unless the chilled water pump runs continuously or the
chilled water system contains a suitable concentration of anti-
freeze solution. When the cooler pump control is configured
“ON,” the cooler pump relay will be energized when the chiller
enters an “ON” mode (i.e., ON LOCAL, ON TIME, ON
CCN). The cooler pump relay is also energized when certain
alarms are generated. The cooler pump relay should be used as
an override to the external pump control if cooler pump control
is not utilized.
If the cooler pump control relay output is not wired to con-
trol or override the operation of the chilled water pump an OFF
DELAY of 10 minutes must be provided after the chiller is dis-
abled to maintain cooler water flow during the pumpout period.
If cooler pump control is configured “OFF” or “ON” and
the chilled water flow switch/interlock does not close within
5 minutes after the unit is enabled and in an “ON” mode, alarm
A200 will be generated. If cooler pump control is turned “ON”
and the chilled water flow switch/interlock is closed when the
unit is enabled and enters an “ON” mode alarm A202 will be
generated. Alarm A201 will be generated whenever the cooler
pump interlock is open for at least 30 seconds during chiller
operation.
Sensors —
The electronic control uses 4 to 10 thermistors
to sense temperatures for controlling chiller operation. See
Table 2. These sensors are outlined below. See Fig. 7-10 for
thermistor locations. Thermistors T1-T9 are 5 kΩ at 77 F
(25 C). Thermistors T1, T2, T3-T6 and T7-T9 have different
temperature versus resistance and voltage drop performance.
Thermistor T10 is 10 kΩ at 77 F (25 C) and has a different tem-
perature vs resistance and voltage drop performance. See Ther-
mistors section on page 64 for temperature-resistance-voltage
drop characteristics.
Table 5 — Control Methods and Cooling Set Points
*Dual set point switch input used. CSP1 used when switch input is closed. CSP2 used when switch input is open.
†Cooling set point determined from 4 to 20 mA input to Energy Management Module (EMM) to terminals TB6-3,5.
CONTROL
TYPE
(CTRL)
OCCUPANCY
STATE
COOLING SET POINT SELECT (CLSP)
0
(single)
1
(dual, switch)
2
(dual, 7 day)
3
(dual, occ)
4
(4 to 20 mA)
0 (switch)
Occupied ON,CSP1 ON* ON,CSP1 ON,CSP1 ON†
Unoccupied ON,CSP1 ON* ON,CSP2 ON,CSP2 ON
1 (7 day)
Occupied ON,CSP1 ON* Illegal Illegal ON†
Unoccupied OFF OFF Illegal Illegal OFF
2 (Occupancy)
Occupied ON,CSP1 ON* Illegal Illegal ON†
Unoccupied OFF OFF Illegal Illegal OFF
3 (CCN)
Occupied ON,CSP1 ON* ON,CSP1 ON,CSP1 ON†
Unoccupied ON,CSP1 ON* ON,CSP2 ON,CSP2 ON†