T10 — REMOTE SPACE TEMPERATURE SENSOR —
Sensor T10 (part no. HH51BX006) is an accessory sensor that
is remotely mounted in the controlled space and used for space
temperature reset. The sensor should be installed as a
wall-mounted thermostat would be (in the conditioned space
where it will not be subjected to either a cooling or heating
source or direct exposure to sunlight, and 4 to 5 ft above the
floor).
Space temperature sensor wires are to be connected to ter-
minals in the unit main control box. The space temperature
sensor includes a terminal block (SEN) and a RJ11 female con-
nector. The RJ11 connector is used to tap into the Carrier Com-
fort Network (CCN) at the sensor.
To connect the space temperature sensor (Fig. 11):
1. Using a 20 AWG (American Wire Gage) twisted pair
conductor cable rated for the application, connect
1 wire of the twisted pair to one SEN terminal and
connect the other wire to the other SEN terminal
located under the cover of the space temperature
sensor.
2. Connect the other ends of the wires to terminals 5 and 6
on TB5 located in the unit control box.
Units on the CCN can be monitored from the space at the
sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the CCN (Fig. 12):
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black (–) conductors. (If another wire
color scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the
space temperature sensor.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to table below for
acceptable wiring.
MANUFACTURER
PART NO.
Regular Wiring Plenum Wiring
Alpha
1895
American
A21451 A48301
Belden
8205 884421
Columbia
D6451
Manhattan
M13402 M64430
Quabik
6130
T-55 SPACE
SENSOR
CCN+
CCN GND
CCN-
TO CCN
TERMINALS
ON TB3
AT UNIT
1
2
3
4
5
6
Fig. 11 Typical Space Temperature
Sensor Wiring
Fig. 12 CCN Communications Bus Wiring
to Optional Space Sensor RJ11 Connector