Carrier operating and maintanance Betriebsanleitung Seite 10

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 41
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 9
10
Method 1
Pull the sections against each other, using the pull
ropes attached to the lifting bars. Pull evenly on both
sides of the AHU.
5.2. Connecting Casings of Equal Width
and Height
To connect the AHU sections use one of the follo-
wing methods. The method depends on the AHU
construction.
Method 1
This method applies for sections that end in joint
mullions:
• Check that the four corners are attached.
Figure 14.
Joint mullions with linking corner pla-
ces
- Ensure that the sealing tape supplied is fixed to
one of the two sections, before moving the sections
against each other.
Then place the anti-vibration mats where the next
casing section will be positioned and then place
this section.
Before placing the sections against each other, fix
the sealing tape supplied between the sections. This
should be done in four places, and the sealing tape
should overlap at the corners See Figs 17 and 21.
The labels which show the matching surfaces are for
making easy the matching of unit surfaces correctly
during assembly of AHU. Same numbers should be
side by side.
NOTE: Attach the sealing tape supplied to only one
of the two assembled sections.
- Place the sections as close together as possible.
Ensure that both sections can still be moved. Insert
a lifting bar into both sections, so that they can be
pulled closer towards each other.
There are two methods for pulling the sections to-
wards each other:
Method 2
Insert a bar with threaded ends through both lifting
bar holes. Screw a nut onto the threaded ends of the
bar and tighten it. Tighten it evenly on both sides of
the AHU.
Figure 11.
Linking the casing sections with pull
ropes
Figure 12.
Linking the casing section with a bar
NOTE: Before connecting the sections, they should be
horizontally and vertically aligned, using infill plates. If
the floor is not completely level, first place the casing
section that will be on the highest part of the floor.
Figure 13.
Unit of equal width and length
Seitenansicht 9