Check once a year for contamination, and if neces-
sary clean with compressed air. Check the connec-
tions in the control box. Check the operation of the
thermostat.
The following warning pictograms are located on the
panel:electrical voltage and hot surface.
Check once a year for contamination and if necessary
clean with compressed air against the direction of the
air flow or clean with a vacuum cleaner. The elimina-
tor assembly after the cooler is removable. Check for
leakage. Check the fins of the droplet eliminator after
the coil. Clean the siphon and check its operation.
Check the condensate pan for contamination and
clean if necessary.
Check the rotor once a year for contamination, and if
necessary clean with compressed air. Check the rotor
speed and compare it with the design data.
Check the operation of the rotation monitor. Depend-
ing on the rotor material the wheel can absorb mois-
ture. When stationary the wheel will become moist on
one side and thus heavier. The rotor speed can be
set to intermittent in the controller so that the wheel
will rotate “x”times per time unit.
The rotor bearings are lubricated for life and do not
require maintenance. The drive motor is accessible
via an inspection cover.
The V-belt is automatically tensioned by a spring-
loaded rocking base on which the motor is installed.
New belts expand a lot in the beginning. Check after
two days if the belt still has enough tension. After this
check the belt tension weekly during the first month
and then check it once a month.
For further operation and maintenance details on the
heat recovery wheel/controller refer to the documenta-
tion provided by the supplier. The following warning
pictogram is located on the panel:rotating parts.
12.9.2. Electric Heaters
12.11. Heat Recovery Wheel
1 - SAFETY CONSIDERATIONS
1.1 - General
The 39HQ air handling units (AHUs) has been designed
and manufactured in accordance with the CE machine
directive EN292. In order to guarantee safe operation and
use of the unit, please carefully read and observe the
instructions in this document and pay special attention to
the warnings that apply to this unit. Any modifications in
the design and/or installation of the AHU that are carried
out without discussion with Alarko Carrier and
without advance written agreement will result in the loss of
the right to any warranty claims and any claim for injury to
personnel as a result of these modifications.
Maintenance procedures may only be carried out by
qualified personnel.
Heating and cooling elements are manufactured and
supplied in accordance with guidelines of the Pressure
Equipment Directive (PED).
1.2 - Applications
The AHU is designed for the movement and conditioning
of air, unless otherwise agreed during the design stage.
1.3 - Instruction types
The following warning pictograms and labels with text are
used.
Lifting point
This pictogram shows where the AHU must be lifted and is
positioned on the support beam.
Lifting prohibited
This pictogram shows that no horizontal transport devices
must be placed under this frame section, such as pallet
lifters or the forks of fork lift trucks. It is also forbidden to
place lifting devices for transport and storage under this
frame element.
Earthing
This pictogram indicates where the AHU must be earthed
and is on one of the support beams beneath the casing in
the fan section.
- The electrical components in the AHU must be earthed,
except for components with double insulation and/or
components with a supply voltage below 50 V.
- The electrical components must be installed in accordance
with national and local regulations.
Rotating parts
This pictogram indicates that there are rotating parts behind
this access cover, door or panel which may cause injury. The
components that include rotating parts are the fan and heat
recovery wheel. If there are special customer-specific
components behind doors, access covers or panels that
include rotating parts and pose a potential risk, this is also
indicated by this pictogram.
Hot surfaces
This pictogram indicates that there are components behind
this access cover, door or panel that can cause serious burns
when touched.
The components that may have hot surfaces are the steam
humidifier, steam heater and the electric heater. If there are
special special customer-specific components behind doors,
access covers or panels that have hot surfaces and pose a
potential risk, this is also indicated by this pictogram.
4
Electrical voltage
This pictogram indicates that there are electrical components
behind this access cover, door or panel that may be dangerous
for the user/installer. Only personnel qualified in accordance
with NEN 3140 is permitted to carry out work on these
components. The pictogram is attached to the access cover
for the electric heater control box.
Removal of transport brackets
This pictogram is located at the bottom of the fan section. It
indicates that the transport brackets must be removed during
commissioning before the fan is started up.
Verwijder transportbeugels voor opstarten ventilator.
Remove transport brackets before starting up the fan.
Retirer les fixations de transport avant démarrage.
Central data
This label contains the data for the AHU, such as order
number, position number etc. If present, the label is normally
located on the access cover or the door of the fan assembly.
Opening the fan door
This pictogram is positioned on the outside of the door or
access cover of the fan assembly. This pictogram warns that
the fan must have been switched off and deenergised for a
minimum of two minutes before the door or access cover is
opened.
Lifting and transport
An instruction is attached to the AHU that describes the
procedures that must be followed for lifting and transport.
The following chapter contains further details.
1.4 - Disposal of parts/materials
- The packaging material must be disposed of in a responsible
manner and in accordance with local regulations.
- Components that are replaced, must be disposed of as
described above.
2 - TRANSPORT AND LIFTING INSTRUCTIONS
2.1 - General
Transport and lifting of the AHU must always be in
accordance with the instructions below. If these instructions
are not observed, irreparable damage may occur to the unit,
and people in the immediate vicinity of the unit are also
endangered. Alarko Carrier does not accept any
responsibility if these instructions are not observed. Transport
and lifting must be carried out by qualified personnel. The
AHU must only be lifted with lifting bars supplied by
Alarko Carrier. Lifting must be carried out in
accordance with local regulations and with the help of
certified lifting aids.
2.2 - Transport and storage
Lifting of the AHU is only permitted under the designated
lifting points. Lifting under the cross beams is prohibited.
This applies to transport as well as storage, and is indicated
on the cross beam with the following label.
! WARNING!
Before opening doors, switch off and deenergise the
fan, and ensure that it has stopped rotating.
(minimum of 2 minutes)
.
5
Caution: All doors and access covers must be closed before
starting up the AHU.
12.10. Coolers
1 - SAFETY CONSIDERATIONS
1.1 - General
The 39HQ air handling units (AHUs) has been designed
and manufactured in accordance with the CE machine
directive EN292. In order to guarantee safe operation and
use of the unit, please carefully read and observe the
instructions in this document and pay special attention to
the warnings that apply to this unit. Any modifications in
the design and/or installation of the AHU that are carried
out without discussion with Alarko Carrier and
without advance written agreement will result in the loss of
the right to any warranty claims and any claim for injury to
personnel as a result of these modifications.
Maintenance procedures may only be carried out by
qualified personnel.
Heating and cooling elements are manufactured and
supplied in accordance with guidelines of the Pressure
Equipment Directive (PED).
1.2 - Applications
The AHU is designed for the movement and conditioning
of air, unless otherwise agreed during the design stage.
1.3 - Instruction types
The following warning pictograms and labels with text are
used.
Lifting point
This pictogram shows where the AHU must be lifted and is
positioned on the support beam.
Lifting prohibited
This pictogram shows that no horizontal transport devices
must be placed under this frame section, such as pallet
lifters or the forks of fork lift trucks. It is also forbidden to
place lifting devices for transport and storage under this
frame element.
Earthing
This pictogram indicates where the AHU must be earthed
and is on one of the support beams beneath the casing in
the fan section.
- The electrical components in the AHU must be earthed,
except for components with double insulation and/or
components with a supply voltage below 50 V.
- The electrical components must be installed in accordance
with national and local regulations.
Rotating parts
This pictogram indicates that there are rotating parts behind
this access cover, door or panel which may cause injury. The
components that include rotating parts are the fan and heat
recovery wheel. If there are special customer-specific
components behind doors, access covers or panels that
include rotating parts and pose a potential risk, this is also
indicated by this pictogram.
Hot surfaces
This pictogram indicates that there are components behind
this access cover, door or panel that can cause serious burns
when touched.
The components that may have hot surfaces are the steam
humidifier, steam heater and the electric heater. If there are
special special customer-specific components behind doors,
access covers or panels that have hot surfaces and pose a
potential risk, this is also indicated by this pictogram.
4
Check the plate heat exchanger once a year for con-
tamination and if necessary clean with compressed
air against the direction of the air flow. If dampers are
used, follow the instructions in section 10.6.
Check condensate pan for contamination and clean
if necessary.
Clean the pollutant trap in the steam supply of the
control valve once a year. If a pollutant trap is installed,
clean the condensate drain valve and the inside of
the condensate pan at the same time.
Inspect the control valve, condensate drain and
distribution box twice a year. With steam distribution
pipes in negative pressure systems (air-side) there
may be excess water present, as the condensate may
not drain from the steam distribution pipe. For some
brands a special siphon with a check valve is supplied.
Check the operation of this valve twice a year.
At the periodical checks of the steam humidifier the
casing sections after the humidifier facilitate the
checking of the humidification level. Viewed in the
direction of the air flow there should not be any
steam plume at the end of the steam humidification
section.
The electric humidifier capacity is strongly affected by
contamination of the steam boiler and the electrodes.
This is indicated on the LED. If necessary replace
steam boiler.
For further operation and maintenance details on the
steam humidifier refer to the documentation provided
by the supplier.
The following warning pictograms are located on the
panel:hot surface.
12.12. Plate Heat Exchanger
12.13. Water Humidification
12.13.1. Steam Humidifier
1 - SAFETY CONSIDERATIONS
1.1 - General
The 39HQ air handling units (AHUs) has been designed
and manufactured in accordance with the CE machine
directive EN292. In order to guarantee safe operation and
use of the unit, please carefully read and observe the
instructions in this document and pay special attention to
the warnings that apply to this unit. Any modifications in
the design and/or installation of the AHU that are carried
out without discussion with Alarko Carrier and
without advance written agreement will result in the loss of
the right to any warranty claims and any claim for injury to
personnel as a result of these modifications.
Maintenance procedures may only be carried out by
qualified personnel.
Heating and cooling elements are manufactured and
supplied in accordance with guidelines of the Pressure
Equipment Directive (PED).
1.2 - Applications
The AHU is designed for the movement and conditioning
of air, unless otherwise agreed during the design stage.
1.3 - Instruction types
The following warning pictograms and labels with text are
used.
Lifting point
This pictogram shows where the AHU must be lifted and is
positioned on the support beam.
Lifting prohibited
This pictogram shows that no horizontal transport devices
must be placed under this frame section, such as pallet
lifters or the forks of fork lift trucks. It is also forbidden to
place lifting devices for transport and storage under this
frame element.
Earthing
This pictogram indicates where the AHU must be earthed
and is on one of the support beams beneath the casing in
the fan section.
- The electrical components in the AHU must be earthed,
except for components with double insulation and/or
components with a supply voltage below 50 V.
- The electrical components must be installed in accordance
with national and local regulations.
Rotating parts
This pictogram indicates that there are rotating parts behind
this access cover, door or panel which may cause injury. The
components that include rotating parts are the fan and heat
recovery wheel. If there are special customer-specific
components behind doors, access covers or panels that
include rotating parts and pose a potential risk, this is also
indicated by this pictogram.
Hot surfaces
This pictogram indicates that there are components behind
this access cover, door or panel that can cause serious burns
when touched.
The components that may have hot surfaces are the steam
humidifier, steam heater and the electric heater. If there are
special special customer-specific components behind doors,
access covers or panels that have hot surfaces and pose a
potential risk, this is also indicated by this pictogram.
4
For maintenance details on the spray humidifier refer
to the documentation provided by the supplier.
12.13.2. Spray Humidifier