Chiller Maintenance
Lesson Plan
#:
NMH30C000105
pulleys or cable. The guide vane actuator seemed to respond to manual control when
disconnected from
the crank arm linkage.
HVAC Technicians removed the guide vane actuator linkage arm in preparation for pulling the
suction
pipe spool that contains the guide vane mechanism. The technicians noticed a streak of thread
sealer
from the crank arm to the bearing housing yoke for the guide vane shaft. The bearing housing yoke
was
removed and the presence of thread sealer was noted on the guide vane shaft and bearing
housing.
It was discovered that the thread sealer applied under CMWO 2845865 had seeped along the
guide vane
shaft and into the guide vane shaft bushing housing. The thread sealer got between the guide
vane shaft
and the bearing housing yoke. This caused a large drag between the guide vane shaft and the
bushing
housing. The guide vane shaft was no longer free to rotate and resulted in the guide vane actuator
being
unable to respond the changing system cooling demand. The apparent cause of this incident was
too
much thread sealer applied to the set screw threads for the guide vane shaft which contributed to
the
excess sealer being allowed to migrate along the shaft to the bushing housing.
CRDR 3409841
Unit two B normal chiller tripped on low of pressure on start up.
Closed ball valve on oil supply line was not restored after oil filter replacement.
The refrigerant was removed from the machine so there is no advantage to closing the valve to
replace filters.
P.M. now have work instructions to verify the valve is opened before starting chiller.