Chiller Maintenance
Lesson Plan
#:
NMH30C000105
This modification will require two adjustments.
Change the oil sump temperature setpoint:
The se tpoint cha nge require s the chille r to be shutdow n w hile the controlle r is being a djusted.
Remove the cover from the oil sump temperature controller.
Adjust the oil sump temperature setpoint to 155°F ± 5°F.
Verify that the oil sump temperature controller is cycling the heater on and off to maintain
temperature.
Adjust lube oil cooler temperature control valve:
The control valve adjustment will require the chiller to be in operation while the oil cooler outlet
throttle valve is adjusted to the higher temperature range.
Remove the administrative control lock on the oil cooler outlet valve.
Adjust the oil cooler outlet valve to maintain oil sump temperature 15F ± F.
Replace the administrative control lock on the oil cooler outlet valve.
What could cause the chiller to trip on low oil pressure?
CRDR# 2934843 Document an occurrence of a U-2 Essential chiller trip due to restricted oil
flow.
On October 17, 2006, HVAC had completed maintenance on 2MECBE01, Essential C hiller and
returned the Chiller to Operations. This maintenance included replacement of the oil pump
filters.
Two filters are utilized on the oil pump. They are installed in tandem (i.e. one stacked
on top of the other). Loose woven felt gaskets are placed on the top and bottom of each
filter. The filters are inserted into the filter canister and rest on top of a spring. A cone
shaped tube slightly protrudes down from the mounting area; this assists in aligning the
upper filter and gasket onto the mounting area. Once aligned the technician must exert
upward pressure, to overcome the spring tension, while sliding the filter canister over the
O-ring seal and hold the filter canister housing against the mounting area. Next the
technician must screw on a collar to secure the assembly in place. Access to this work
area is restricted; piping and supports hamper access and obscure the technician vision.