hermostatic Valve Control, 4-Pipe — The 4-pipe system
provides the ultimate in economy and room temperature con-
trol. Both hot water and chilled water are available at any time.
Normally an automatic changeover thermostat is used, but a
manual changeover thermostat is also suitable. Two 2-way
valves, two 3-way valves, or one 2-way plus one 3-way valve
must be selected. An automatic changeover device to sense
water temperature is not required.
With this system, the fan runs continuously unless it is
manually switched to OFF/AUTO position. Fan must be on be-
fore thermostat can send signal to open the chilled water or hot
water valve.
NOTE: Wiring diagrams are for typical applications. If other
voltages for heaters or controls are specified, wiring may differ
from that shown. See Fig. 92 for line voltage control. See
Fig. 93 and 94 for 24-v control. Refer to wiring diagram on
unit blower housing for unit specific wiring.
Fig. 92 — 42C,S,V (except VG), and 42D (600-1000 cfm) 4-Pipe Heating and Cooling —
Remote/Wall-Mounted Thermostat (Line Voltage)
ONLY 120V WHT/ALL
OTHERS BLK