Fig. 38 — Return-Air Wall Panels for Furred-In Units — Panels with Frame Dimensions
INSTALLATION
Step 1 — Place Units in Position
42C UNITS
1. Select the unit location. Allow adequate space for free air
circulation, service clearances, piping and electrical
connections, and any necessary ductwork. For specific
unit dimensions, refer to Fig. 1-12. Allow clearances ac-
cording to local and national electric codes.
2. Make sure ceiling is able to support the weight of the unit.
See Table 1 for nominal unit weight.
3. Ensure bottom panel has been removed from 42CG, CK
units with mounting holes. When unit is lifted, access to
the 0.375-in. mounting holes is through the bottom of the
unit. Hanger rods and fasteners and other required hard-
ware must be field-supplied.
4. Move unit into position. Ensure unit is level or pitched
towards drain to ensure proper drainage and operation.
Pitch of suspended unit can change after coil is filled;
recheck after filling coil.
5. Mounting unit:
a. Use rods and fasteners to suspend the unit at the
factory-provided mounting holes with rubber
grommets on the top of the unit on 42CG, CK
units. Reach into unit and attach unit to the ceiling
using the 0.375-in. mounting holes (4) in top
panel; do not use any other locations.
PANEL NO. 5 WITH CONTROL DOOR
60.4
A
PANEL NO. 4
54.7
A
PANEL NO. 4 FOR 42SU
51.7
A
PANEL AND FRAME DIMENSIONS (in.)
NOTE: Dimensions in inches.
PANEL NO. UNIT UNIT SIZE A
4
42SG,SJ,
SU
03, 04 15.1
06, 08 19.1
10, 12 23.1
5 42SG,SJ
03, 04 15.1
06, 08 19.1
10, 12 23.1
A42-4168
A42-4276
A42-4277
PANEL NO. 5 WITHOUT DOOR
60.4
A
A42-4273