MOUNTING THE ROOM CONTROLLER (Fig. 15-17) —
Unscrew the side fixing screw. Open the room controller rear
mounting base to expose the mounting holes. The base can be
removed to simplify mounting (snap apart carefully at hinge to
separate mounting base from the rest of the room controller).
Route the room controller wires through the large hole in the
mounting base. Level the mounting base against the wall (for
aesthetic value only, as the room controller does not need to be
level for proper operation) and mark the wall through the two
mounting holes. Drill two
3
/
16
in. mounting holes in the wall
where marked. Secure the mounting base correctly (UP) to the
wall with the two screws and two anchors provided, (additional
anchoring holes are available for more secure mounting if nec-
essary) making sure all wires extend through the hole in the
mounting base. Adjust the length and routing of each wire to
reach the proper terminal in the connector block on the mount-
ing base, with
1
/
4
in. of extra wire (strip only
1
/
4
in. of insulation
from each wire to prevent adjacent wires from shorting togeth-
er when connected).
Match and connect equipment wires to proper terminals
in the connector block. Both power and communication
wires must be connected correctly for proper room controller
operation.
Push any excess wire into the wall and against mounting
base. If the air sensor is being used on the room controller, seal
the hole in the wall to prevent air leaks. Leaks can affect sensor
operation.
Push the room controller snap hinge to the base and tighten
the side fixing screw.
4-1/4" (108mm)
0mm)7("4/3-2
3/4"(20mm)
Fig. 14 — Room Controller Dimensions
Mounting screws
G
P
C
Fig. 15 — Mounting the Room Controller
Connection Cable
G
P
C
Connection Cable
G
P
C
Fig. 16 — Locating the Connection Cable
Fig. 17 — Connecting the Room Controller