The condensate may be discharged at a maximum height of
7
7
/
8
in. above the unit, as long as the ascending tube is vertical
and aligned with the drainage flange.
If it is necessary to discharge the condensate from a level
above 7
7
/
8
in., install an auxiliary water discharge pump and
float valve. A float valve is recommended to stop the compres-
sor if there is a fault at the auxiliary pump.
The condensate pipe must be insulated with condensation
proof material such as polyurethane, propylene or neoprene of
3
/
16
in. to
3
/
8
in. thickness. See Fig. 10.
NOTE: If more than one unit is installed in the room, the drain
system can be designed as shown in Fig. 10.
Installing the Grille and Frame Assembly
— Carefully un-
pack the assembly and check for damage sustained in transport.
Attach the assembly to the unit by using the two hooks. See
Fig.11. Tighten the four screws, link the electrical connectors
and insert the wires in the cable clamp. Use the screws supplied
to fix the frame in to position. See Fig. 12.
Ensure that the frame is not distorted by excessive tighten-
ing, that it is aligned with the false ceiling and that there is a
seal between the air inlet and outlet. See Fig. 13. Gasket “A”
prevents return air from mixing with the supply air and gasket
“B” prevents the supply air from leaking into the ceiling void.
Once the unit is mounted in the ceiling, the gap between the
unit frame and the false ceiling must not be more than
3
/
16
in.
wide.
The drain tube extension must be securely fastened to the
condensate drain. Failure to do so could result in conden-
sate water dripping on to the floor, which could cause per-
sonal injury.
Washer
Threaded hangers
Washer
Nut
Nut
Nut
Wooden frame
Threaded hangers
Washers
Nut
Threaded hangers
"T" bar
(to be removed)
Supension Brackets
Supension Brackets
Threaded Hangers
T-Bar
T-Bar
Threaded Hangers
T-Bar
Fig. 4 — Positioning Unit
Fig. 5 — Attaching Hangers to Ceiling
Fig. 6 — Threaded Hangers and T Bar
Fig. 7 — Positioning Unit in Ceiling
False
Ceiling
Spirit
Level
1 to 1-3/16
Indoor
Outdoor
3/16"
÷
3/8"
(5
÷
10 m
m
)
"4/
3-2
÷
"3
m 08/0
7(
m)
Fig. 8 — Align and Level the Unit
Fig. 9 — Drilling for Connections