Step 3 — Locating and Mounting the Room
Controller
LOCATING THE ROOM CONTROLLER — See Fig. 14
for room controller dimensions. If the air sensor in the room
controller is going to be used, the room controller should be
located by considering the following:
Position controller with a minimum clearance of 5 ft from
the floor.
Locate the unit in the same area as the fan coil unit; prefera-
bly on an inside partitioning wall.
Locate on a section of the wall without pipes or ductwork.
Do not locate close to a window, on an outside wall, or next
to a door leading to the outside.
Do not locate where the controller is exposed to direct light
and heat from a lamp, sun, fireplace, or other temperature-
radiating object that may cause a false reading.
Do not locate close to, or in direct airflow of, a heating or
cooling supply.
Do not locate in areas with poor circulation, such as behind
a door or in an alcove.
NOTE: Do not exceed 500 ft of network wiring when mount-
ing the room controller.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
7-7/8”(200 mm)
2%
2” (50 mm)
m
a
x.
Frame support brackets
Power connection
cables from frame
Power connection
cables from unit
Safety cord
Cable clamp
Frame support
screws
Fig. 10 — Condensate Drain Pipe
Fig. 11 — Attach Frame Assembly
Fig. 12 — Fix Frame in Position
A AIR B
A. Gasket "A"
B. Gasket "B"
Fig. 13 — Gasket Location