INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNPACK UNIT (See Fig. 1) — Move the unit to final loca-
tion. The grille panel and the remote control are separately
packed for maximum protection. Remove unit from carton, be-
ing careful not to lift the unit by the condensate drain discharge
pipe or by the refrigerant connections. Handle by the four
corners of the unit. See Table 1 for field-supplied materials
required for installation.
INSPECT SHIPMENT — File a claim with the shipping
company if shipment is damaged or incomplete. Check the unit
nameplates to ensure units match job requirements.
CONSIDER SYSTEM REQUIREMENTS — Consult local
building codes and NEC for special installation requirements.
Use only designated indoor units with outdoor units. See
Tables 2-4B.
See Fig. 2 for unit dimensions. Allow sufficient space for
airflow clearance, wiring, refrigerant piping, and servicing
units.
Avoid mounting the unit in areas that are:
• exposed to direct sunlight
• too close to heat sources
• damp or areas exposed to water
• located in areas that could obstruct air circulation, such
as near curtains or furniture
Table 1 — Field Supplied Installation Materials
LEGEND
Table 2 — Matching Indoor Units to Outdoor Units*
*All units use R-410A refrigerant only.
Table 3 — AccuRator* Control Sizes and Refrigerant Charge Requirements
*AccuRator controls are for outdoor units. See the outdoor installation instructions for more information.
†The outdoor unit is either fully charged or under charged from the factory.
NAME SPECIFICATIONS
Connection Pipe
40KMC018,024,KMQ01824:
5
/
8
in. (Mixed Phase)/
3
/
8
in. (Liquid)
40KMC/KMQ03036:
3
/
4
in. (Mixed Phase)/
3
/
8
in. (Liquid)
Wall Sleeve —
Wall Cap —
Finishing Tape PVC Film
Fastening Tape —
Tube Insulation —
Drain Hose 1 in. ID
Sealer Putty —
Outdoor Power Supply Cable
40KMC018-036: AWG 14
40KMQ018-036: AWG 12
Control Wire Electrical Connecting Cable
Between Indoor and Outdoor Unit
Cable Type: AWG 22 synthetic rubber insulation with
Neoprene coating, according to NEC codes.
Wire nuts —
Conduit —
AWG — American Wire Gage
NEC — National Electrical Code
SYSTEM
TYPE
SYSTEM SIZE
OUTDOOR
UNIT
INDOOR UNIT
MODEL NUMBER
INDOOR UNIT
GRILLE ITEM NUMBER
Cooling Only
018 38HDF018 40KMC018---3 40KMC9005
024 38HDF024 40KMC024---3 40KMC9006
030 38HDF030 40KMC03036---3 40KMC9006
036 38HDF036 40KMC03036---3 40KMC9006
Cooling with
Electric Heat
018 38HDF018 40KMQ01824-3 40KMC9006
024 38HDF024 40KMQ01824-3 40KMC9006
030 38HDF030 40KMQ03036-3 40KMC9006
036 38HDF036 40KMQ03036-3 40KMC9006
Heat Pump
018 38QRF018 40KMQ01824-3 40KMC9006
024 38QRF024 40KMQ01824-3 40KMC9006
030 38QRF030 40KMQ03036-3 40KMC9006
036 38QRF035 40KMQ03036-3 40KMC9006
SYSTEM
TYPE
SYSTEM
SIZE
COOLING
ACCURATOR
HEATING
ACCURATOR
ACCURATOR
TYPE
FACTORY
CHARGE† (lb)
ADDITIONAL FIELD
CHARGE REQUIRED† (lb)
Cooling Only
018 0.049 — B 4.8 0.0
024 0.057 — B 5.3 1.2
030 0.061 — B 5.0 3.0
036 0.074 — B 7.0 2.3
Cooling with
Electric Heat
018 0.049 — B 4.8 0.0
024 0.057 — B 5.3 1.2
030 0.061 — B 5.0 3.0
036 0.074 — B 7.0 2.3
Heat Pump
018 0.051 0.046 B 5.5 0.0
024 0.055 0.053 B 6.9 0.0
030 0.063 0.055 B 10.7 1.8
036 0.07 0.063 B 10.5 0.0