DRAIN CONNECTIONS
Install drains to meet the local sanitation codes. If adequate gravity
drainage cannot be provided, a field installed condensate pump
accessory should be used. Refer to the Installation Instructions of
the condensate pump for detailed specifications.
NOTE: The high wall fan coils have internal condensate trap.
An external trap is not required.
Drain connections may be routed through alternate locations as
shown in Fig. 11.
Pipe holder
Pipe cover
Right piping
Left piping
Pipe cover
Right back piping
Left back piping
1
2
3
4
A09112
Fig. 11 – Piping Locations
WIRING
The main power is supplied to the outdoor unit. Four field supplied
connecting cables from the outdoor unit to each of the indoor units
are: L1, L2, Ground, and S for communication between the
outdoor unit and each indoor unit.
CONTROL SYSTEM
The 38/40GVM unit is equipped with a microprocessor control to
operate the system and give optimum levels of comfort and
operating efficiency.
There are microprocessor boards and thermistors located in both
the indoor and outdoor units. The thermistors monitor the system
operation and control the operating mode. The change in the
settings or the modes of operation, use the factory supplied
wireless remote control.
The 38/40GVM unit has the following operating modes:
S Fan Only
S Auto
S Heating (on Heat Pumps only)
S Cooling
S Dehumidification (Dry)
FAN ONLY -- In Fan Only mode, the system filters and circulates
the room air without changing the room air temperature.
AUTO -- In Auto mode, the system will automatically select one of
the following operating modes: cooling, heating or fan only based
on the difference between the room temperature and the set point
temperature.
HEATING -- In the Heating mode, the system heats and filters
room air.
COOLING -- When in Cooling mode, the fan runs all the time and
the system cools, dries and filters room air.
DEHUMIDIFICATION (DRY) -- in Dehumidification (Dry)
mode, the system dries, filters and slightly cools room temperature.
This mode does not take place of a dehumidifier.
In addition to the above modes that are selected by using the
remote control, the unit can run in emergency mode by using a
manual button. This mode is used when the remote is misplaced or
the batteries in the remote have died. In this mode, the unit will run
in AUTO mode with a predetermined set point (76_F/24.4_C)
WIRELESS REMOTE CONTROL
1. A wireless remote control is supplied for system operation.
2. Each battery--operated wireless remote control may be used
to control more than one unit.
3. The wireless remote control has a range of 25 ft. (7.6 m).
SEQUENCE OF OPERATION
Simultaneous heating and cooling is not allowed. At start--up, the
first indoor unit to call for operation (heating or cooling) will
control from the preset position, the mode of operation for the rest
of the indoor units connected to the same outdoor unit. If the other
units conflict in mode with the first unit an error message will be
displayed on those units.
When a unit is set to COOL, HEAT or DRY mode, the electronic
expansion valve is first initialized (closed) and then is opened to a
preset position.
Superheat heat for each fan coil (the ones that are energized) is
monitored and the position of the electronic expansion valve is
adjusted to ensure that each fan coil gets the appropriate amount of
refrigerant to maintain the required superheat. After the set point is
satisfied and the fan coil shuts off, the electronic expansion valve
stays open for a specified time to ensure that system pressures
equalize.
When the system is set for COOL, HEAT or DRY mode, the
compressor speed is varied by comparing the indoor air
temperature with the set point and continuously adjusting the
compressor speed (to keep the compressor running as long as
possible) in an effort to maintain the greatest comfort possible.
The indoor fan can be running in MANUAL or AUTO mode.
When the fan is running in AUTO mode, the speed is determined
by comparing the room temperature to the set point.
In COOLING mode, when the set point is satisfied, the fan will
continue running. In HEATING mode, when the set point is
satisfied, the fan speed will be reduced and then will run
continuously until the coil temperature drops to a point cold air is
blown on the occupants in the space, at which time the indoor fan
is de--energized.
When the unit goes through the defrost cycle, the indoor fans are
de--energized and the refrigerant is circulated through all the fan
coils (even if they were off or on standby before the defrost cycle)
to maximize the heat transfer surface area available for defrost
operation.