FIELD WIRING
Field wiring is shown in Fig. 25-37.
LEGEND FOR FIG. 25-37
ALM — Alarm
C—Contactor
CFC — Condenser Fan Contactor
CPR — Condenser Pump Relay
CWP — Chilled Water Pump
DSIO — High Voltage Relay Module
EQUIP — Equipment
EXV — Electronic Expansion Valve
FU — Fuse
GFI-CO — Ground Fault Interrupter Convenience Outlet
GND — Ground
NEC — National Electrical Code
PL — Plug
PSIO — Processor Sensor Input/Output Module
RB — Relay Board
TB — Terminal Block
Field-Wired
Factory Wired
FIELD CONTROL POWER SUPPLY
NEC FUSED DISCONNECT
230 V CONTROL CIRCUITS
USE 15 AMP MAXIMUM FROM
SEPARATE POWER SUPPLY
115 V CONTROL CIRCUITS
USE 30 AMP MAXIMUM FROM
SEPARATE POWER SUPPLY
2
1
GND
TB4
Fig. 25 — Power Supply Wiring
EQUIP GND
TB2
TB2
BLK
BLK
T1
T2
K6
SEPARATE
115 OR 230 V
FIELD POWER
SUPPLY
RELAY BOARD 1
2
3
ALM
MAX. LOAD ALLOWED FOR THE ALARM RELAY IS
125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
FIELD SUPPLIED
Fig. 26 — Remote Alarm Relay Accessory Wiring; 30HXA,C
RELAY BOARD 2
K3
T4
T3
SEPARATE
115 OR 230 V
FIELD POWER
SUPPLY
EQUIP GND
ALM
MAX. LOAD ALLOWED FOR THE ALARM RELAY IS
125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
FIELD SUPPLIED
Fig. 27 — Remote Alarm Relay Accessory Wiring; 30GX
68