Carrier start-up and Spezifikationen Seite 59

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 100
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 58
to the high side. Transfer refrigerant and reclaim any refrig-
erant remaining in the low side.
NOTE: A new packing nut and ferrule will be required as
the old one is not removable from the old thermistor.
For 30GX080-176 and all 30HX units cut wire nuts apart
to appropriate blue leads at PSIO-1 (J7-5,6 for T3; J7-8,9 for
T4) and red leads connecting wires to TRAN-7. Remove old
leads from control box harness. For 30GX205-265 units, dis-
connect plug assembly at liquid level sensor. Loosen the pack-
ing nut fully from the well threads. Remove and discard old
thermistor and packing nut. Slide new packing nut then fer-
rule up onto new thermistor probe from inserted end. Inser-
tion depth is dependent on unit model number. See Fig. 22
and Table 41.
Hand tighten packing nut to position ferrule while hold-
ing thermistor in position. With wrench, tighten enough to
firmly secure thermistor in place in well. Run new harness
wires into main control box for 30GX080-176 and all 30HX
units. Reconnect blue wires at PSIO-1 for thermistor read-
ing and red wires to TRAN-7. Reconnect plug assembly to
new liquid level sensor for 30GX205-265 units. Restore unit
control power only and verify that level thermistor is read-
ing correctly. Check system low side for leaks and repair as
necessary. Evacuate low side and open circuit discharge and
liquid valves.
To service compressor motor thermistors:
Two thermistors are factory installed in each compressor.
Connections for the thermistors are located in the compres-
sor junction box. There are 3 terminals for the thermistors:
S1, S2, and C. Motor temperature is measured by leads con-
nected to one of the S terminals and the C terminal. If a com-
pressor motor thermistor failure occurs, verify that there is
a true short or open circuit at these terminals. If one of the
thermistors fails, disconnect and relocate the wire on one of
the S terminals to the other S terminal (S1 to S2 or S2 to S1).
The thermistors are not serviceable in the field. If both of the
compressor motor thermistors fail, compressor replacement
is required. See Table 40 for motor thermistor temperature
and resistance values.
Pressure Transducers A single style of pressure
transducer is used for both high- and low-pressure sensing
on the 30GX,HX chillers. The transducers operate on a
5 vdc supply. The power supply for this is a 24 vac to
5 vdc full wave rectified power supply, PS1. See unit com-
ponent arrangement label for mounting location and termi-
nal connections in the control box. Refer to Fig. 23A and
23B for pressure transducer locations.
PRESSURE TRANSDUCER CALIBRATION Pressure
transducers are factory installed on all models to read Dis-
charge, Suction, Economizer (reads leaving condenser pres-
sure on models without economizer), and Oil pressure. DO
NOT attempt to calibrate any of these transducers by the pres-
sure gage method unless the transducer is connected to a fully
charged refrigerant system. A more accurate method of cali-
bration is used by the 30GX,HX software and corrects for
ambient temperature when calibrating. Calibrating a trans-
ducer when the system is under nitrogen charge will result
in an incorrect offset being applied to the reading (due to
temperature correction). Although these transducers are cali-
brated at the factory, replacement transducers require cali-
bration for accurate readings. Calibration is also required when
replacing a PSIO. Access to the transducer calibration area
is through the Service function and the transducers can
be calibrated at the current system pressure using a pressure
gage at the same point or exposed to atmospheric pressure.
In the example in Table 42, the Circuit A Discharge Pressure
transducer has been replaced and needs to be calibrated. A
pressure gage has been installed at the transducer and reads
85 psi (must be in the range of −5.0 to 185.0 psi). See
Table 42.
Use care when removing the oil pressure transducers from
the compressor fitting. The fitting that the transducers
mount in is sealed with an O-ring Schrader fitting into
the compressor casting. Do NOT overtigthen the trans-
ducer when replacing after calibration. Hold both fit-
tings with wrenches when removing and reinstalling.
The control will apply the 0.8 psi offset from the calibra-
tion example in Table 42 to all future readings. The cali-
bration process for any of the other pressure transducers is
done in a similar manner. A transducer can also be calibrated
at atmospheric pressure by removing the transducer from the
system. To do this, carefully unplug the transducer connec-
tor. Unscrew the transducer from its mounting location and
reconnect the connector. Follow the steps in Table 42 to read
the current pressure and enter 0.0 psig as the gage pressure.
Remove the connector from the transducer, thread the trans-
ducer back onto the fitting from which it was removed (do
NOT use thread sealant/compound), and reinstall the
connector.
If it is necessary, all of the transducers may be calibrated
at 0.0 psig. All of the transducers must be removed from the
system and reconnected in atmosphere as described.
When complete, scroll down under to ‘Calibrate
All at 0 PSIG’ and press . A ‘Yes’ will be dis-
played at this step and will automatically change back to ‘No’
once all transducers have been successfully calibrated. Re-
connect the transducers and connectors as described above.
All transducers are mounted on Schrader fittings. Therefore,
it is NOT necessary to remove system refrigerant charge.
Use a catch pan when removing the oil pressure transducer
for calibration as oil will leak out through the Schrader
fitting.
TROUBLESHOOTING If transducer is suspected of be-
ing faulty, first check supply voltage to transducer. Supply
voltage should be 5 vdc ± .2 v. If supply voltage is correct,
compare pressure reading displayed on keypad and display
module against pressure shown on a calibrated pressure gage.
If the 2 pressure readings are not reasonably close, replace
pressure transducer.
59
Seitenansicht 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 99 100

Kommentare zu diesen Handbüchern

Keine Kommentare