Features/Benefits (cont)
Carrier Cycle-Guard™ anti-
crystallization controls maintain
proper solution concentration
The 16JB automatically limits solu-
tion concentration in several ways to
avoid both crystallization and overdilu-
tion to provide dependable, trouble-
free operation. Crystallization of the
lithium bromide solution depends
on the combination of temperature
and concentration. Carrier’s Cycle-
Guard concentration control sys-
tem automatically monitors the refrig-
erant water level in the evaporator
in conjunction with the solution tem-
perature returning to the absorber.
Because concentration varies with the
amount of water in the lithium bro-
mide solution, a rising evaporator
level indicates less water in the solu-
tion and thus a higher solution concen-
tration. When the refrigerant in the
evaporator rises to a preset level,
water is transferred from the evapora-
tor to the absorber, thus preventing
overconcentration to ensure
continuous, reliable operation even at
cooling water temperatures as low
as 55 F (12.8 C).
The 16JB also incorporates a
simple, passive method of control to
correct any crystallization that would
normally start to occur on the
shellside of the low temperature solu-
tion heat exchanger under abnor-
mal conditions. As the hot solution
begins to back up in the generator as
a result of any shellside blockage, it
rises above the overflow pipe and
returns directly to the absorber. It is
subsequently pumped through the
tubeside (heating the shellside) to
restore proper operation. In addition
to this passive method of control,
the 16JB PIC advanced crystallization
protection senses any impending
abnormalities in the operating cycle
and self corrects and/or limits the
chller from any possibility of crystalli-
zation, adding another layer of protec-
tion and reducing chiller down time.
In addition, the 16JB automatic
dilution cycle ensures proper concen-
tration after a scheduled unit shut-
down so that the unit will not crystallize
when the machine cools to ambient
or machine room temperature. The
dilution cycle controls operation of the
pumps until the refrigerant drops to
a predetermined level and the dilution
level switch opens. The opening of
the dilution level switch deenergizes
the pumps after shutdown. This dilutes
the solution to prevent an overcon-
centration condition. Crystallization is
also minimized by the gravity drain
feature of the generator on the 16JB.
The force of gravity and top-mounting
of the generator above the absorber
enable the strong solution to drain out
of the generator should a power out-
age occur.