Carrier 16JB Bedienungsanleitung Seite 2

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 28
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 1
Single, reliable operation The
16JB absorption chiller employs a
single generator to provide one stage
of solution reconcentration, making
it the most basic of the cycles available
today. Simplicity of design, combined
with its numerous other quality fea-
tures, equates to inherently high reli-
ability. Few moving parts and simple,
dependable operation reduce down-
time, as well as service and main-
tenance costs. The 16JB chiller offers
typical full-load steam rates of ap-
proximately 18 lb/hr-ton at standard
ARI (Air Conditioning and Refrig-
eration Institute) operating
conditions.
Superior part-load performance
The 16JB’s standard concentration
control system allows stable, part-
load operation at cooling water tem-
peratures as low as 55 F (12.8 C)
without the need for a cooling tower
bypass. In addition, a control valve
ensures stable, continuous evaporator
pump operation at part-load condi-
tions. The 16JB has a continuous
operating range from 100% to10% of
machine capacity.
Application versatility
Designed to suit a variety of appli-
cations The use of steam or hot
water from a number of sources allows
the 16JB machine to meet a variety
of cooling needs. Waste heat sources
generated from industrial processes
and cogeneration systems can be uti-
lized to provide chilled water for
process cooling as well as comfort
cooling, reducing the need for
purchased energy and contributing to
even greater energy savings.
Ideal for new or retrofit applica-
tions Whether intended for re-
placement of existing chiller systems
or for new construction purposes, the
16JB is well suited to meet the needs
of almost any cooling application. The
16JB’s 15 model sizes, spanning a
capacity range of 108 to 680 tons,
make the 16JB single effect absorption
chiller the ideal choice for comfort
cooling and/or light industrial applica-
tions. Carrier’s computerized perfor-
mance ratings assist in the selection of
the appropriate machine, properly
sized to meet exact job requirements.
Dependable operation, as well as
low sound and vibration levels, en-
sures occupant comfort, even when
installed on upper floors.
Combine absorption and
electric-driven chillers Utilizing
both absorption and electric chillers in
a central plant offers the flexibility to
base load one chiller, while using
the other to handle peak load require-
ments. Hybrid chiller systems have
proven to be an economical solution
for many comfort cooling installations.
In many geographical areas, operat-
ing the electric chiller as the base
loaded machine, while utilizing the
absorption chiller during peak load
conditions, avoids or reduces electric
demand charges. Depending on utility
rate structures, a 16JB single effect
absorption chiller used in conjunction
with an electric-driven chiller may
be the most efficient and cost-effective
combination available.
Location and installation
savings
Ease of installation All 16JB’s
are completely fabricated, assem-
bled, and wired in the factory as single
piece units. Standard shipping con-
figuration is either 1- or 2-piece(s),
depending on size. Refer to the 16JB
Standard Shipping Configuration
table below.
16JB STANDARD SHIPPING
CONFIGURATION
SIZE 1-PIECE 2-PIECES
010-047 X
054-068 X
Model sizes through 16JB047 ship
completely assembled as standard with
an option for 2-piece shipment. The
2-piece shipment is ideal for retro-
fit or replacement installations where
access into the equipment room
may be limited. The 16JB054-068
machines ship in 2 pieces as standard
for easier handling and rigging. Job-
site re-assembly and alignment of
units shipped in 2 sections is simpli-
fied by pre-erecting the machine in
the factory and incorporating
weld-type assembly flanges on all
interconnecting piping.
Table of contents
Page
Features/Benefits .................................................1-7
Model Number Nomenclature ........................................2
Options and Accessories ............................................8
Machine Components ............................................9,10
Physical Data ...................................................11,12
Dimensions ......................................................13
Performance Data ................................................14
Application Data.................................................15,16
Electrical Data ..................................................17,18
Controls ........................................................19-21
Typical Piping and Wiring ..........................................22
Guide Specifications .............................................23-28
Model number nomenclature