8
\\MAINMENU\TEMP
Current path in the menu structure
ROOMT 25.3°C
List of items
SPOFFSET 0.3^C
Cursor position
OAT 35.0°C
SAT 19.2°C
SCT_A 57.0°C
Room Setpoint Oset
Description of the item framed by
the selection cursor
The Up and Down arrow keys position the cursor on the
current menu item. The Enter key activates the parameter
modification (if possible). Any non-pertinent modification
attempt is blocked by a refusal screen.
A configuration parameter can be modified by positioning
the cursor and then pressing the Enter key.
\\MAINMENU\SETPOINT Current path in the menu structure
roomtocc 21.0°C
List of items
roomtuno 28.0°C
Cursor position
satmin 14.0°C
satmax 30.0°C
potreset 3^C
Room T, unoccupied
Description of the item framed by
the selection cursor
The following screen allows modification of a parameter.
Modify value Screen description
roomtuno
28.0 °C
Current value
_ °C
Cursor position
Room T, unoccupied
Item description
The Up and Down arrow keys permit the selection of the
first digit. Pressing the Up key successively scrolls up to
the following symbols:
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, ., -.
The Down key follows the reverse order of the Up key in
scrolling down the digit list above. Each digit is validated
with the Enter key.
The - sign is only accessible for the first selected character.
Modify value Description of the screen
roomtuno
28.0 °C
Current value
27.5_ °C
Cursor position
Room T, unoccupied Item description
The value is validated with the Enter key. At any time the
return key cancels the current modification.
ATTENTION: If the user exits from the current data screen,
the value is saved. A saving confirmation is displayed.
The Enter key validates the parameter modification(s).
The Return to the Previous Screen key cancels the current
modification(s).
\\MAINMENU\SETPOINT Current path in the menu structure
Save changes? Conrmation that the modication is
saved
The unit is in Local Off mode, pressing the on/off (0/1) key
once activates the display of the operating mode screen.
Select Machine Mode Description of the screen
Local On List of the machine operating
modes
Local Schedule Cursor
CCN
Remote
The Up and Down keys position the cursor on the selected
operating mode. Four modes are immediately displayed on
the screen. To access operating modes that are not visible,
please use the Up and Down keys.
When the operating mode has been selected, the new
operating mode can be validated with the Enter key.
Command accepted Operating mode validation screen
When the unit is in an operating mode and the On/off key
is pressed, the unit will stop. A confirmation screen protects
the unit against inadvertent shutdowns.
PRESS ENTER Machine shutdown conrmation
screen
TO CONFIRM STOP