Pressure sensors
Two types of electronic (high and low-pressure) sensors
are used to measure the suction and discharge pressure in
each circuit.
Thermistors
The outdoor temperature sensor is installed under a metal
plate. The compressor suction gas temperature sensors are
installed just upstream of the compressor.
If temperature sensor control is selected:
• The NTC 10 K room temperature sensor must be placed
in a position that is representative of the room tempera-
ture. Avoide exposure to the sun or to humidity.
• The NTC 5 K supply air sensor must be placed in a
position that is representative of the supply air tempe-
rature (downstream of the evaporator).
Solenoid valves
Two solenoid valves must be installed on the liquid line of
each circuit to permit pumpdown of the circuit during
shut-down.
Alarm LED
An LED installed at the front of the control box displays
the unit alarms.
Alarm reset button
A push button installed at the front of the control box
permits resetting all activated unit alarms.