Seitenansicht 5
6
Physical data
30GV/30GY 020 025 030 035 044*** 049*** 059***
Nominal cooling capacity 30GV* kW 51 66 73 97 132 146 193
Nominal cooling capacity 30GY* kW 50 69 97 101 138 153 202
Operating weight kg 850.0 1030.0 1100.0 1250.0 2111.5 2255.0 2562.5
Refrigerant charge**** kg 9.8 14.5 15.2 17.0 29.0 29.0 34.0
Compressor Semi-hermetic, 4 or 6 cylinders, 24.2 r/s
Quantity
Circuit A/B 1/- 1/- 1/- 1/- 1/1 1/1 1/1
No. of capacity steps 2 2** 2** 2** 3 3 3
Capacity control % 50/100 66/100 66/100 66/100 33/66/100 33/66/100 33/66/100
Evaporator Coaxial Shell-and-tube
Net water volume l 21.7 31.0 31.0 43.0 62.0 62.0 86.0
Water connections in BSPC, conical gas, ISO R7
Inlet 2-1/2 MPT 2 FPT 2 FPT 2 FPT 3 FPT 3 FPT 3FPT
Outlet 2-1/2 MPT 2 MPT 2 MPT 2 MPT 3 FPT 3 FPT 3FPT
Max. water side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000
Condenser Copper tubes, al;uminium fins
Condenser fan Single centrifugal Double centrifugal Two, double centrifigal
Nominal air flow l/s 3500 5600 5600 6900 11200 11200 13800
Speed at 150 Pa ESP r/s 10.33 10.33 10.67 10.53 10.33 10.67 10.83
Nominal fan motor power kW 3.0 4.0 4.0 4.5 2 x 4.0 2 x 4.0 2 c 4.5
Motor speed r/s 24.2 24.2 24.2 24.2 24.2 24.2 24.2
* Based on 12°C/7°C entering/leaving chilled water temperature, 35°C condenser entering air temperature and nominal fan speed.
** 3 steps with capacity reduction accessory
*** Supplied as two separate units as follows, with all electrical, hydraulic and mechanical components necessary for installation: size 044 = 2 x size 025, size 049 = 2 x
size 030, size 059 = 2 x size 035
**** 30GY units use refrigerant R-22, 30GV units use R-407C. The refrigerant charge shown is guidelines only. Always refer to the nameplate.
Electrical data
30GV/30GY Standard unit Fan
150 Pa 300 Pa (optional)
XL PW
V-ph-Hz RLA ICF ICF kW FLA kW FLA
020 230-3-50 62 263 163 3.7 11.7 4.9 15.7
400-3-50 36 180 111 3.7 6.3 4.9 9.0
025 230-3-50 84 359 222 4.9 15.7 8.8 26.4
400-3-50 48 232 143 4.9 9.0 8.8 15.2
030 230-3-50 94 383 237 4.9 15.7 8.8 26.4
400-3-50 54 262 161 4.9 9.0 8.8 15.2
035 230-3-50 135 564 346 5.5 17.9 8.8 26.4
400-3-50 77 356 218 5.5 10.3 8.8 15.2
044 230-3-50 167 442 305 9.8 2 x 15.7 17.6 2 x 26.4
400-3-50 96 280 191 9.8 2 x 9.0 17.6 2 x 15.2
049 230-3-50 187 476 330 9.8 2 x 15.7 17.6 2 x 26.4
400-3-50 108 316 215 9.8 2 x 9.0 17.6 2 x 15.2
059 230-3-50 270 699 808 11.0 2 x 17.9 17.6 2 x 26.4
400-3-50 154 433 295 11.0 2 x 10.3 17.6 2 x 15.2
Legend:
FLA - Full load amperes
ICF - Maximum instantaneous current flow, A (compressors)
kW - Maximum fan motor power input
RLA - Rated load amperes (compressors)
PW - Part-winding astart (compressors)
XL - Across-the-line-start (compressors)
Note: To obtain the maximum unit current, add the compressor maximum currecnt (RLA) to the fan motor current (FLA).