15
minute. If a zone fails to receive updates from the linkage mas-
ter for 5 sequential times (greater than 5 minutes without suc-
cessful communications), then a Linkage Failure communica-
tion alarm is generated. The alarm is generated from the zone
that indicated loss of communication with Linkage Master. To
determine when communications have returned to normal, the
controller will continue to monitor the communication status.
After 5 sequential successful communications, then a return to
normal message is generated, although normal operation will
resume after the first successful communication.
Linkage Failure (Failure to Communicate with
Air Source) —
If a zone controller has been configured as
the linkage master, and an air source address has been config-
ured to a value other than the default, then the linkage master
zone controller will exchange information with the configured
air source once each minute. The air source must be Linkage
compatible.
If the air source fails to respond, then the linkage master will
attempt to retry communication. If unsuccessful, the linkage
master will log the attempt as a failure. If 5 sequential failures
occur (more than 5 minutes without successful communica-
tion), then a Linkage Failure communication alarm is generat-
ed for the air source. The alarm indicates a Linkage Air Source
Failure at address X, X (where X, X is the failed air source ad-
dress). To determine when communications have returned to
normal, the controller will continue to monitor the communica-
tion status. After 5 sequential successful communications oc-
cur, a return to normal message is generated.
Supply Air Temperature Sensor Failure —
For any
zone where ducted heat is configured, if the supply air tempera-
ture sensor fails then a Supply Air Temperature Sensor Failure
alarm for that zone is generated. The zone controller will wait
2 minutes before generating the alarm. A return to normal (or
reset of the time delay) occurs immediately upon the detection
of a normal temperature or if the ducted heat is configured
to No.
Primary Air Temperature Sensor Failure
—
For
any linkage master where the air source address is NOT con-
figured (default value), if the primary air temperature sensor
fails then a Primary Air Temperature Sensor Failure alarm is
generated. The alarm is generated after a 2 minute delay. A re-
turn to normal (or reset of the time delay) occurs immediately
upon the detection of a normal temperature or if an air source
address is configured.
Pressure Sensor Low Airflow Pressure
Alarm
—
Any time the value of the input channel voltage
falls below a minimum acceptable value (0.89 V), then a Low
Airflow Pressure alarm will be generated for that zone. For all
control types except Dual Duct or Room Pressure Control, the
alarm indicates an Airflow Sensor Low Pressure alarm.
For Dual Duct and Zone Pressure Control applications, both
primary airflow and secondary airflow sensors are monitored
for this condition. The appropriate alarm message is generated,
based upon the sensor failure detected.
To determine when normal conditions have returned, the
zone controller will continue to monitor the input. When the
voltage rises to within tolerance (above 0.91 V), a return to nor-
mal message is generated.
NOTE: A value of 0.89 volts is the minimum acceptable 0 in.
wg value.
Pressure Sensor High Velocity Pressure
Alarm —
Any time the calculated value of the measured ve-
locity pressure exceeds the configured maximum value for
more than 5 minutes, then a High Velocity Pressure alarm is
generated for that zone. The range is 0.250 in. wg to 2.000 in.
wg. The default is 1.200 in. wg. For Dual Duct and Room
Pressure Control applications, both primary airflow and sec-
ondary airflow sensors are monitored for this condition. The
appropriate alarm message is generated, based upon the appro-
priate sensor measurement.
The zone controller will continue to monitor the input, and
when the pressure falls below the alarm limit minus 0.1 in. wg,
a return to normal message is generated.
Relative Humidity Sensor Alarm
—
If the control-
ler is configured for Relative Humidity control and the value of
the sensor exceeds the Relative Humidity High alarm limit or
falls below the Relative Humidity Low alarm limit during oc-
cupied periods, then an alarm is generated. The condition must
exceed the alarm limit for 5 minutes before the zone controller
will issue the alarm.
The alarm will be generated only if Humidity Control is En-
abled. A delay is applied whenever the control transitions to an
occupied mode or if the control set point is changed in order to
prevent false alarms. The delay is similar to the Space Temper-
ature Alarm Limit Delay. The low Relative Humidity alarm
has a configurable range from 0% to 100% and a default of
20%. The high Relative Humidity alarm has a configuration
range from 0% to 100% and a default of 70%. A fixed hystere-
sis of 2% is used to determine when the conditions have re-
turned to normal. Alarms can be generated during occupied
and unoccupied times.
I
AQ Sensor Alarm
—
If the zone controller is config-
ured for IAQ control and the value of the sensor exceeds the
IAQ High Alarm Limit or falls below the IAQ Low Alarm
Limit during occupied periods, then an alarm is generated. The
alarm condition has a delay of 5 minutes before the alarm to be
generated.
The alarm is generated only if the IAQ control is Enabled.
A 2-hour delay is applied whenever the zone controller transi-
tions to an occupied mode, in order to prevent false alarms. The
low IAQ alarm limit has a configuration range of 0 to 5000
(ppm) with a default of 0. The high IAQ alarm limit has a con-
figuration range of 0 to 5000 (ppm) with a default of 2000. For
flexibility, the limits for the IAQ alarm do not include units, but
the IAQ sensor alarm descriptions (24-character text) include
the default units (‘PPM’) as part of the description.
To determine when normal conditions have returned, the
zone controller will apply a 2% hysteresis to the alarm limits,
and generate a return to normal message when the sensor re-
turns within range (2% of the alarm limit value).
Failure to Zero Calibrate Pressure Trans-
ducer
—
During the zero calibration procedure, if the air-
flow pressure input voltage fails to decrease to within the al-
lowable zero pressure range, the zone controller will generate a
Failure to Zero Calibrate Pressure Transducer alarm.
Damper Position and Actuator Installation
—
During the damper calibration procedure of the Commission-
ing Mode or during the zero calibration, after the damper is
driven closed, the control will generate a Damper Actuator
Failure to Close alarm if the corresponding damper position is
not within the specified closed position range. The acceptable
input voltage range is above 8.5 VDC for clockwise open and
below 1.5 VDC for counterclockwise open. The damper posi-
tion sensor has a 0 to 10 range.
CCN USER INTERFACE
The Points Display Table, Set Point Table, and Linkage
Maintenance Table are shown to inform a user of what infor-
mation is available to be accessed via CCN user interface,
BEST++, DataPort, DataLink and BacLink Gateway. See
Tables 7-9.
→
801
Kommentare zu diesen Handbüchern