Carrier 33ZCSECTRM Spezifikationen Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 44
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
13
The schedule master broadcasts its occupancy status upon
transition and every 15 minutes, whenever it is configured as a
global schedule (schedule number 65 to 99).
All the controllers on any CCN bus that are using the same
global schedule need to be configured for the same schedule
number.
Remote Occupancy Contact —
The remote occu-
pancy contact can be used to provide a room occupancy sensor
input to the zone controller. If the remote occupancy contact in-
put is in the off position the zone controller will transition to
unoccupied. If the remote contact input is in the on position the
zone controller will follow its local occupancy schedule.
Occupancy Override —
The occupancy function will
support a timed override function. The timed override will be
activated through the space temperature sensor override button.
If the override is activated in a zone that is receiving a global
time schedule, then the override will be reported to the device
issuing the global schedule. The device will then update the oc-
cupancy status of the zones receiving the schedule.
NOTE: All zones sharing a global occupancy schedule will be
overridden to the occupied mode if any one of the space tem-
perature sensors report an override. For zones that require indi-
vidual overrides, those zones will have to use a local schedule.
Manual Occupancy Override Function —
By us-
ing a CCN user interface, the user is able to command a timed
override by entering the number of hours of override hours (0
to 4 hours). A manual entry greater than 0 will bring the zone
controller schedule into the occupancy mode. This function is
defined as manual override.
If the occupancy schedule is occupied when the manual
override is downloaded, the current occupancy period will be
extended by the number of hours downloaded. If the current
occupancy period is unoccupied when the occupancy override
is initiated, the mode will change to occupied for the duration
of the number of hours downloaded.
If the occupancy override is due to end after the start of the
next occupancy period, the mode will transition from occupan-
cy override to occupied without becoming unoccupied, and the
occupancy override timer will be reset.
An active manual occupancy override or a pending occu-
pancy override may be canceled by downloading a zero to this
configuration. Once a number other than zero has been down-
loaded to this configuration, any subsequent downloads of any
value other than zero will be ignored by the zone controller.
Once the override period has expired, the value is reset to 0
and the manual override function is complete. If the override is
activated in a zone utilizing local occupancy scheduling, then
only that zone is affected. The override will occur for the time
configured for that device.
Occupancy Table Format —
The occupancy table is
common to both a local and global occupancy function. For
flexibility of scheduling the occupancy programming is split
into eight separate periods. The configuration consists of eight
fields corresponding to the seven days of the week and a holi-
day field in the following order: Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday Sunday, Holiday. The occupancy
time is configured in hour and minutes in military time.
The format of the schedule and the calculations performed
on the schedule data is shown in Fig. 5.
Optimal Start Operation —
For local occupancy, the
occupancy function will factor in the occupancy bias time sup-
plied by the linkage function. This bias time will cause the oc-
cupancy period to start earlier by the amount indicated by the
bias time. The occupancy function will provide information so
that the rest of the zone controller functions can differentiate
between biased occupied periods and configured occupied
periods.
The Start Bias Time (in minutes) is calculated by the air
source as needed to bring the temperature up or down to meet
the set point under the optimal start routine. This value will be
sent to all associated zones for optimal start of zone controllers.
SYSTEM OVERRIDE MODES
The system will react to four override modes reported by
the air source compatible with linkage: pressurization, evacua-
tion, nighttime free cooling (NTFC), and morning warm up.
Pressurization —
In Pessurization mode, the system will
bring in as much outside air as possible in order to pressurize the
area. This mode is used for smoke control and prevents smoke
from entering into an area that is adjacent to an area of smoke.
Each zone controller will modulate its damper to provide
maximum cooling airflow into the space. If the terminal con-
tains a series fan, the fan will be turned on. If the terminal con-
tains a parallel fan it will be turned off. If the terminal contains
auxiliary heat, the heating will be controlled so as to maintain
the current heating set point. Secondary dampers in a zone
pressurization application will closed.
Evacuation —
In Evacuation mode, the system will at-
tempt to remove smoke from an area by creating a negative
pressure. Either a return air fan in the air source, or some other
fan mechanism will be used to exhaust the smoke filled return
air from the space. The terminals will respond by closing their
dampers and turning off all fans. Secondary dampers in a zone
pressurization application will open.
Night Time Free Cooling (NTFC) —
In NTFC mode,
the system is attempting to use cool night time (3 AM to 7 AM)
outside air to cool down the space. In this mode, the air source
will operate its fan and mixed air dampers to provide outside
air to the system. The air terminals will act as if they are in the
Occupied Cooling mode except that the temperature control set
point will be the midpoint between the occupied cooling and
heating set points rather than the occupied cooling set point.
Morning Warm-Up —
In Morning Warm-up mode, the
air source provides central heating. Morning warm-up will run
once per day and will start at the time indicated by the earliest
occupied zone (biased by the optimal start calculation). If VAV
central heating is enabled, then the zone controller will modu-
late air flow between the minimum and maximum heating cfm
limits to achieve its occupied heating set point.
SET POINT GROUPING
Each zone controller will contain a set point schedule. This
schedule will contain temperature, humidity, and air quality set
points. The set point data may be unique to the zone controller
or multiple zone controllers may be grouped together to share
the same temperature set points.
The controller contains a Set Point Group Number configu-
ration parameter and a Set Point Group Master configuration
parameter. When a zone controller is configured as Set Point
Master, the zone controller will broadcast its set points to other
zone controllers that are configured to accept the Broadcast Set
Point Schedule. If a zone controller is not configured to use
global set points, the zone controller will use its own onboard
set point schedule. The Set Point Master is independent of the
Master Linkage zone controller. There can be 16 Set Point
Group functions per CCN bus. Global set points will not be
transmitted through CCN bridges.
SPACE TEMPERATURE SHARING
Each zone controller has the capability to share its local sen-
sor and temperature offset with other zone controllers. Each
801
Seitenansicht 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 43 44

Kommentare zu diesen Handbüchern

Keine Kommentare