actuator preassembled to housing
capable of demand controlled ventilation
capable of individual zone pressure control for individ-
ual supply and exhaust control in conjunction with sec-
ondary terminal controller (required)
easy access to airflow sensor pneumatic connections
capable of high-speed 38.4 kilobaud communications
network operation
128 controller maximum system (must be located on
same Carrier communicating network bus segment)
capable of zone humidity control (dehumidification)
Carrier Linkage System compatibility
global set point and occupancy scheduling
capable of local set point adjustment with field-installed
temperature sensor (with temperature offset)
both controller housing and actuator are UL94-5V ple-
num rated
The zone controller is a single duct or fan powered, variable
air volume (VAV) terminal control with a factory-integrated ac-
tuator. The zone controller maintains precise temperature con-
trol in the space by operating the terminal fan and regulating
the flow of conditioned air into the space.
Buildings with diverse loading conditions can be supported
by controlling reheat, ducted heat, or non-ducted supplemental
heat. The zone controller can support two-position hot water,
modulating hot water, or up to 3-stage electric heat.
With the addition of a secondary exhaust or return air termi-
nal and the 33ZCSECTRM controller, zone pressurization
applications can be supported.
Supply and exhaust airflow control is provided on an
individual zone basis in order to maintain the desired zone
pressure.
The 33ZCSECTRM in conjunction with the fan terminal
zone controller are used to provide control for constant volume
dual duct applications.
When linked to a Carrier Linkage System, the zone control-
ler provides numerous features and benefits such as weighted
average demand for system operation, intelligent supply air
temperature reset, set point averaging, global set point sched-
ule, and occupancy scheduling. Duct static pressure reset for
the air source is provided, based on terminal requirements.
The zone controller provides additional control features
such as Occupied/Unoccupied scheduling initialized via the
network. The zone controller offers override invoked from a
wall sensor during unoccupied hours from 1 to 1440 minutes in
1-minute increments. Optional indoor air quality (IAQ) or rela-
tive humidity monitoring and control are also available.
The zone controller assembly contains an integral VAV ac-
tuator that is field mounted to the VAV terminal damper shaft,
similar to the mounting of a standard actuator. The actuator is
rated at 35 in.-lb (3.95 Nm) torque, a 90-degree stroke, and
provides a 90-second nominal running time at 60 Hz. The actu-
ator is suitable for mounting onto a
3
/
8
-in. (9.5 mm) square or
round damper shaft, or onto a
1
/
2
-in. (13 mm) round damper
shaft. The minimum damper shaft length is 1
3
/
4
in. (45 mm).
The zone controller is designed for vertical or horizontal
mounting.
The zone controller is provided with removable connectors
for power and communications. The zone controller has non-
removable screw type connectors for inputs. The removable
connectors are designed so that they can be inserted one
way so as to prevent installation errors. The zone controller
also provides an RJ-11 modular phone jack for the Network
Service tool connection to the module via the Carrier network
communications.
An optional conduit box cover (Part Number
33ZCCONBOX) allows field wiring connection via conduit.
The conduit box is designed to accept two
1
/
2
-in. (13 mm)
EMT (Electrical Metal Tubing) conduits.
The 33ZCFANTRM is designed to allow a service person
or building owner to configure and operate the unit through the
Carrier proprietary network user interfaces. A user interface is
not required for day-to-day operation. All maintenance, config-
uration, setup, and diagnostic information is available through
the Level II communications port to allow data access by an at-
tached computer running Network Service Tool, Comfort-
VIEW
TM
, or ComfortWORKS
®
software.
WIRING CONNECTIONS — Field wiring is 18 to 22 AWG
(American Wire Gage). The zone controller is a NEC (National
Electrical Code) Class 2 rated device.
INPUTS
space temperature sensor
primary air damper position (factory-installed)
airflow sensor (factory installed)
field-installed remote wall sensor set point adjustment
optional supply temperature sensor (required for ducted
heat and supply air monitoring)
optional primary air temperature sensor (one per system
is required for systems which do not utilize a linkage
compatible air source)
optional IAQ sensor or relative humidity sensor
optional secondary airflow (zone pressure or dual duct)
optional remote occupancy contact
OUTPUTS
internally factory-wired damper actuator
heating (ducted or non-ducted)
— modulating (floating) heat
— up to 3 stages of electric heat
— two-position heat
fan start/stop
secondary damper actuator
POWER SUPPLY — The 33ZCFANTRM requires a 24 vac
± 10% power source rated at 40 va (50/60 Hz).
POWER CONSUMPTION — The power requirement siz-
ing allows for accessory water valves and for the fan contactor.
Water valves are limited to 8 va on both two-position and
modulating hot water. The fan contactor is limited to 11 va
(holding).
NOTE: If a water valve or fan contactor exceeds these limits,
or external contactors are required for electric heat, then it is
recommended a 60 va transformer be used. The maximum rat-
ing for any output is 20 va.
ACCURACY Terminal airflow (nominal cfm) is rated at
1 in. wg (249 kPa) measured velocity pressure. The zone con-
troller is capable of controlling to as low as 10% or as high as
125% of nominal airflow with an accuracy of ± 3% (nominal)
at any point within the range.
HARDWARE (MEMORY)
FLASH EPROM
DIFFERENTIAL PRESSURE RANGE — 0 to 2.0 in. wg
(0 to 498 kPa) maximum for the onboard flow sensor.
SPECIFIED SENSING TEMPERATURE RANGE — The
zone controller space temperature, supply temperature, and pri-
mary air temperature sensing range is –40 to 245 F (–40 to
118 C). The zone controller has an allowable control set point
range from 40 to 90 F (4 to 32 C) for heating and 45 to 99 F
(7 to 37 C) for cooling.
COMMUNICATIONS The number of controllers is limit-
ed to 128 zones maximum, with a limit of 8 systems (Linkage
Coordinator configured for at least 2 zones). Bus length may
not exceed 4000 ft (1219 m), with no more than 60 devices on
any 1000 ft (305 m) section. Optically isolated RS-485 repeat-
ers are required every 1000 ft (305 m).
At 19,200 and 38,400 baud, the number of controllers is
limited to 128 maximum, with no limit on the number of Link-
age Coordinators.