Seitenansicht 4
5
Modulating hot water valve
Combination radiant/ducted heat stages
Terminal fan (requires VVT® Zone Controller Option
Board)
Damper position output (0 to 10 v) for linked dampers
WIRING CONNECTIONS — Field wiring is 18 to 22 AWG
(American Wire Gage). The VVT zone controller is a NEC
(National Electronic Code) Class 2 rated device.
POWER SUPPLY The 33ZCVVTZC-01 zone controller
requires a 24 vac ± 10% at 40 va (60 Hz) power source.
COMMUNICATIONS The number of controllers is limit-
ed to 128 devices maximum, with a limit of 8 systems
(Linkage Coordinator configured for at least 2 zones). Bus
length may not exceed 4000 ft (1219 m), with no more than
60 devices on any 1000 ft (305 m) section. Optically isolated
RS-485 repeaters are required every 1000 ft (305 m).
At 19,200 and 38,400 baud, the number of controllers is
limited to 128 maximum, with no limit on the number of Link-
age Coordinators. Bus length may not exceed 1000 ft (305 m).
ENVIRONMENTAL RATINGS
OperatingTemperature.........32Fto131F(0°Cto55C)
StorageTemperature...........32Fto158F(0°Cto70C)
Operating Humidity. . . . . . . . . . .10% to 95%, non-condensing
StorageHumidity......... 10%to41%at158F,condensing
POWER CONSUMPTION The power requirement siz-
ing allows for accessory water valves and for the fan contactor.
Water valves are limited to 15 va. The fan contactor is limited
to 10 va (holding).
VIBRATION
Performance Vibration:
1.5 G measured at 20 to 300 Hz
CORROSION Office environment. Indoor use only.
APPROVALS
•NECClass2
UL916-PAZXandUL873
Conforms to requirements per European Consortium
standards EN50081-1 (CISPR 22, Class B) and
EN50082-1 (IEC 801-2, IEC 801-3, and IEC 801-4) for
CE mark labeling
UL94-5V (actuator)
Bypass Controller (33ZCBC-01) — The VVT By-
pass Controller is a component of Carriers 3V™ system and is
used to regulate the supply duct static pressure for Variable
Volume and Temperature Applications. The Bypass Controller
is an essential system component that allows constant volume
HVAC equipment to provide zone level temperature control.
The Bypass Controller provides the following features:
System or stand-alone operation
Integrated pressure sensor
Determines system-operating mode
Air source leaving air temperature lockouts
The bypass controller control assembly contains an integral
actuator assembly that is field mounted to the VVT terminal
damper shaft, similar to the mounting of a standard actuator.
The actuator is rated at 35 lb.-in. (3.95 N-m) torque, a
90-degree stroke, and provides a 90-second nominal time at
60 Hz. The actuator is suitable for mounting onto a
3
/
8
-in.
(9.5 mm) square or round damper shaft, or onto a
1
/
2
-in.
(13 mm) round damper shaft. The minimum damper shaft
length is 1
3
/
4
-in. (45 mm). The bypass controller is designed for
vertical or horizontal mounting.
The bypass controller is provided with removable connectors
for power and communications. The bypass controller has non-
removable screw type connectors for inputs. The removable
connectors are designed so that they can be inserted one way so
as to prevent installation errors. The bypass controller also
provides an RJ-11 modular phone jack for the Network
Service tool connection to the module via the Carrier network
communications.
Field-installed actuators may also be used. Belimo Multi-
Function technology actuators may be ordered direct from
Belimo. The following accessory actuators may be used
instead of the integrated actuator:
NM24-MFT US P-30002 70 in.-lb actuators with
floating point control and 0 to 10 vdc feedback.
AM24-MFT US P-30002 160 in.-lb actuators with
floating point control and 0 to 10 vdc feedback.
The following actuators may be used as linked actuators.
Up to four actuators may be linked to the master actuator:
LM24-MFT US P-10002 35 in.-lb actuators with
0 to 10 vdc control and 0 to 10 vdc feedback.
NM24-MFT US P-10002 70 in.-lb actuators with
0 to 10 vdc control and 0 to 10 vdc feedback.
AM24-MFT US P-10002 160 in.-lb actuators with 0
to 10 vdc control and 0 to 10 vdc feedback.
The Bypass Controller operates on the 3V system network
and is compatible with all Carrier communicating devices. A
user interface is not required for everyday operation of the by-
pass controller. The Bypass Controller can be configured or op-
erated through the Carrier Network with optional interface
tools including the System Pilot or Carrier software.
The bypass controller provides the following features and
benefits:
Primary air temperature and pressure sensors determine
system operating mode to ensure proper operation in
case of communication failure.
Air Source leaving air temperature protection minimizes
the occurrence of heating and/or cooling lockouts based
on unacceptable discharge temperatures.
Quick and easy commissioning and balancing process
via a dedicated maintenance table.
Stand-alone or linked system operation
Carrier linkage system capability
Foreign language support for ASCII based character sets
Carrier communicating network
High-speed (38.4K baud) communications network
Thermistor type duct temperature sensor
0 to 2 in. wg pressure sensor
UL94-5V plenum rated controller housing
FUNCTIONS Functions of the bypass controller are:
Auto pressure sensor zero calibration
Manual pressure sensor calibration
High end pressure transducer calibration
Bypass damper calibration
Bypass damper modulation
Leaving air temperature protection
Network tables and alarms
System Pilot interface
INPUTS
Duct temperature sensor
Damper position feedback potentiometer (factory installed)
System pressure (factory installed)
OUTPUTS
Integrated factory-wired pressure dependent damper
actuator
PHYSICAL CHARACTERISTICS
Dimensions..............2.36in.Hx9.2in.Wx4.84in.D
(60 mm x 233.7 mm x 123 mm)
ELECTRICAL CHARACTERISTICS Input Volts 40 va
at 24 vac + 10% (60 Hz)
Seitenansicht 4