Carrier 33ZCVAVTRM Spezifikationen Seite 35

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 40
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 34
35
HOT WATER OR STEAM HEAT — The zone controller
can be configured to control local heat provided by heating coils
carrying hot water or steam, governed either by a two-position
(on/off) valve or by a proportional (floating modulating) valve.
The heating coils can be installed in the air terminal (ducted), or
as perimeter heat. If modulating baseboard is used, refer to the
General Heating Information section for additional information.
Figure 22 shows the hardware configuration for a zone control-
ler applied to a series fan powered air terminal equipped with
hot water or steam heating coils. The diagram in Fig. 23 shows
how the zone controller controls an air terminal equipped with
two-position hot water or steam heat. The diagram in Fig. 24
shows how the zone controller controls an air terminal equipped
with proportional hot water or steam heat. The fan runs con-
stantly in all modes during occupied periods.
For modulating control, the supply air needed is compared
to the actual supply air to either drive the valve open or closed.
There is a deadband on the supply air deviation where the valve
will be left at the current position until the error gets larger than
the deadband.
For modulating type heat, the floating point function com-
pares the submaster reference from the PID loop to the supply
air temperature to calculate the direction and time to position
the valve. The control prevents both outputs from operating
simultaneously.
Configuration determines the logic output type for normally
open or normally closed type two-position valves.
HeatingwithIAQControl
A feature is provided for situa-
tions in which additional primary air is required for ventilation
(IAQ).
The heating set point is calculated from the midpoint be-
tween the current heating and cooling set points.
The standard heating algorithm is used. The algorithm pre-
vents the space temperature from falling below the set point
before heating is activated. The air terminal must be in the
cooling mode and the equipment must be providing cooling.
When in unoccupied heating, the terminal’s fan will be
turned on to provide airflow to the zone. Also, in the unoccu-
pied mode, the primary damper will be held in its last com-
manded position. If the air source becomes active (on) during
this mode, the damper will be controlled normally.
NOTE: In a Linkage system the when the central fan is operat-
ing, the terminal fan will also be operating.
Parallel Fan Terminal Applications The paral-
lel fan terminal provides three capabilities to the zone. First, it
allows for unoccupied heating if auxiliary heating is available.
Secondly, it allows CV heating when occupied (the fan is on
when ducted heating is on). Thirdly, it provides a means to pre-
vent cold air from “dropping” into the zone during cooling
mode.
The 33ZCFANTRM or 33ZCVVTZC-01 (with option
board) Zone Controllers provide heating control in three differ-
ent ways:
positioning the primary air damper to a minimum air-
flow when the air source is in cooling mode and starting
the fan to utilize plenum heat as a first stage
controlling an optional auxiliary heater mechanism to
provide heating
modulation of the primary air damper when the air
source is in its heating mode (VAV Central Heating)
The 33ZCFANTRM or 33ZCVVTZC-01 (with option
board) Zone Controllers support three methods to control heat-
ing. These methods are as follows:
two-position (on/off) control using a normally open or
normally closed heating valve
modulating control using a normally open or normally
closed floating point heating valve
modulating control using up to 3 stages of electric heat
COOLING The primary control function of zone controller
is to provide cooling to the space by modulating the amount of
supply airflow through its primary damper.
The airflow set point is limited to a range of values that al-
low the air source to operate properly in the Cooling mode.
These configured limits are listed in the Installation Instruc-
tions for the zone controller. The minimum limit ensures that
the sum of all air terminal minimum airflow requirements fall
within the minimum cooling operating range of the air source.
The maximum limit ensures that airflow will not increase
above the maximum design value and that the noise level gen-
erated at this maximum airflow will be acceptable to the occu-
pants of the zone.
100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION
MODE)
MAX HEAT LIMIT
MIN HEAT LIMIT
MIN COOL LIMIT
0%
FULL HEATING
FULL COOLING
DEADBAND
COOL
WARM
OCCUPIED
COOLING
NTFC
SETPOINT
OCCUPIED
HEATING &
MORNING
WARM-UP
SETPOINT
DAMPER
OVERRIDE-
EVACUATION
MODE
3
2
1
ELECTRIC
HEAT
STAGES
<
>
% AIRFLOW
SPACE TEMPERATURE (DEGREES)
VENT POSITION
LEGEND
*Stage 1 is radial or baseboard heat with combination heat.
Fig. 21 — Sequence of Operation for Series Fan Powered Air Terminal with Staged Electric Heat
NTFC Nighttime Free Cooling
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
...... Ventilation Mode
NOTE: Ventilation mode occurs when air source mode is in cooling and
air source supply air temperature is above 65 F and below 75 F.
Seitenansicht 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40

Kommentare zu diesen Handbüchern

Keine Kommentare