30
PLENUM
AIR
SUPPLY
AIR
AIRFLOW
SENSOR
DAMPER
ACTUATOR
SUPPLY
AIR
DAMPER
ELEC HEAT
SPACE
TEMPERATURE
SENSOR
NETWORK BUS
ZONE
CONTROLLER
24 VAC
LEAVING AIR
TEMPERATURE
SENSOR
STAGES
RELAY
12
3
LEAVING
AIR
100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION
MODE)
MAX HEAT LIMIT
MIN HEAT LIMIT
MIN COOL LIMIT
0%
FULL HEATING
FULL COOLING
DEADBAND
COOL
WARM
OCCUPIED
COOLING
NTFC
SETPOINT
OCCUPIED
HEATING &
MORNING
WARM-UP
SETPOINT
DAMPER
OVERRIDE-
EVACUATION
MODE
3
2
1
ELECTRIC
HEAT
STAGES
<
>
% AIRFLOW
SPACE TEMPERATURE (DEGREES)
REHEAT LIMIT
VENT POSITION
LEGEND
*Stage 1 is radial or baseboard heat with combination heat.
Fig. 14 — Sequence of Operation for Single Duct Air Terminal with
Staged Electric or Combination Heat
NTFC — Nighttime Free Cooling
Air Source Supplying Heated Air and Zone Controller
is Configured for Central Heating Only
Air Source Supplying Cooled Air
...... Ventilation Mode
*Stage 1 is radial or baseboard heat with combination heat.
NOTE: For 1 or 2 stage heat — use 33ZCVAVTRM. For 3-stage heat — use 33ZCFANTRM.
Fig. 13 — Single Duct Air Terminal with Staged Electric Heat
NOTE: Ventilation mode occurs when air source mode is in cooling and
air source supply air temperature is above 65 F and below 75 F.