Carrier 33ZCVAVTRM Spezifikationen Seite 27

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 40
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 26
27
Ducted Heat Control (Staged or Modulating
Device)
The zone controller can support a ducted heat
function. The ducted heat function can be configured for either
single duct units, fan powered parallel, or fan powered series
applications where heat needs to be controlled within the zone
that is supplied by the terminal unit.
For this application, heating control loop feedback is re-
quired. The installation of the supply air sensor is required
when the unit is configured for ducted heat.
The zone controller can control a single stage, two-position,
multistage electric heat, or a modulating hot water valve.
When the 33ZCVVTZC-01, 33ZCVAVTRM, or
33ZCFANTRM zone controllers are applied and configured
for heat, and heating is being called for in the space, the zone
controller reads the space sensor and the output is adjusted to
satisfy conditions. The number of stages (if applicable) is
determined by comparing space temperature with the current
biased heating set point.
Configuration determines the logic output type for normally
open or normally closed type two-position valves.
A terminal unit equipped with heating will provide the min-
imum heating cfm configured for the zone whenever the air
source is in heat mode unless VAV central heating is enabled.
The heating control maintains the current heating set point
(plus any offset from a 33ZCT56SPT sensor slide bar during
occupied periods).
Modulating Hot Water/Steam Valve CV The
Modulating Hot Water/Steam Valve CV mode is designed to
use modulating heat valve with a constant volume airflow. This
mode of operation allows all cfm set points to be set to the
same cfm value. The zone reheat will temper the supply air to
maintain proper zone temperature at the configured constant
volume of air.
Central Heating — The use of the zone controller in a
system allows for the application of heating utilizing the heat
from a central air source. The zone controller provides the abil-
ity to add heat to a system during the occupied mode from a
central source. Terminal units designed without any local heat
(ducted or non ducted), should utilize heating. During heating,
the zone controller modulates its primary air damper to provide
heat when the air source is in Heat Mode. The airflow is con-
trolled so that the zone achieves and maintains the desired heat-
ing set point.
NOTE: Central heating is always set to YES on VVT® zone
controllers. No central heating configuration is available if it is
changedtoNO.
In central heating, the terminal provides a variable volume
into the zone. The central supply air will be a source of heating
when the air source is in the heating mode.
For pressure independent applications, the zone controller
temperature control loop determines the airflow set point that is
required to maintain space temperature at the heating set point.
Each zone controller modulates between the minimum heating
cfm and the maximum heating cfm during central heating. This
cfm should be limited to a configured range of values that al-
lows the air source to operate properly in the heating mode.
For pressure dependent applications, the minimum and
maximum damper positions are used to maintain the space
temperature during central heating.
In a system with a Linkage compatible air source, the
zone controller will notify the corresponding linkage coordina-
tor zone controller that the unit is Heat mode.
In the case of a non-Linkage compatible air source, the zone
controller should be set up as the linkage coordinator for
that air source. The zone controller will determine if the
primary-air temperature is greater than the weighted average
space temperature, and if higher, then declares the central air
source in heating.
VAV Central Heating with Ducted Zone Heat
(PI Only)
When heating is available at the zone (ducted),
and central heating is also available, the zone heat will work in
parallel to provide heating to the space. This heating function
provides the required volume of heated air from the central
apparatus. This volume is determined by a PID airflow control,
the space temperature, and the desired set point. In addition, the
temperature of the air can be supplemented by the local heat
source, if the current air temperature cannot meet zone require-
ments. Each zone controller configured for heat (ducted or non
ducted) will operate its heating control loop when ever the
space temperature is below the heating set point to determine a
desired supply air discharge temperature that is necessary to
maintain space temperature at the heating set point.
NOTE: Central heat with ducted zone heat requires a supply
air sensor.
Damper Override — Damper Override mode is initiat-
ed by the air source in response to input from a field-supplied
smoke control panel. When the air source enters an override
mode the linkage coordinator signals the zone controllers to
take corresponding action. The override can take either of two
forms: pressurization or evacuation. In Pressurization mode,
the zone controller commands the air terminal’s supply air
damper to maximum cool cfm. In Evacuation mode, it com-
mands the damper completely closed.
Damper Override supersedes the cfm setting the zone con-
troller would otherwise maintain based on space temperature.
The smoke control panel that commands the override mode
must be in accordance with local codes, as must its installation.
When using central heating, it is the system designers
responsibility that the central apparatus is protected during
heating to provide proper airflow over the central heating
device. Ensure that there will be a minimum system air-
flow that will allow the air source to operate safely in the
heating mode. The zone controller (pressure independent
only) will allow for the option of disabling the central heat-
ing function in a given zone. This means that a central air
source may provide heating for the entire system, or possi-
bly only provide it for those terminals without heat at the
zone level.
Seitenansicht 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 39 40

Kommentare zu diesen Handbüchern

Keine Kommentare