50ZH030-0603-Phase Packaged Heat PumpInstallation, Start-Up and Service InstructionsNOTE: Read the entire instruction manual before starting theinstal
Step 2—Start-Up Cooling Section and Make AdjustmentsComplete the required procedures given in the Pre-Start- Upsection this page before starting the u
TO USE THE COOLING CHARGING CHARTThis method is to be used in cooling mode only. Take the outdoorambient temperature and read the suction pressure gau
Fig. 15—208/230-3-60 Wiring DiagramA0605512
Fig. 16—460-3-60 Wiring DiagramA0605613
Step 6—Sequence of OperationFAN OPERATIONThe FAN switch on the thermostat controls indoor fan operation.When the FAN switch is placed in the ON positi
Table 3—Electrical Data—50ZHUNIT 50ZHSIZE(–SERIES, IFUSED)V-PH-HZVOLTAGERANGECOMPRESSOROFMFLAIFMFLAELECTRIC HEAT SINGLE POINT POWER SUPPLYMIN MAX RLA
The ability to properly perform maintenance on this equip-ment requires certain expertise, mechanical skills, tools andequipment. If you do not posses
a. Lift wheel from housing. When handling and/or cleaningblower wheel, be sure not to disturb balance weights (clips)on blower wheel vanes.b. Remove c
insulation, wiring or air filter(s). For best results, spray outdoor-coil fins from inside to outside the unit. On units with an outer andinner outdoo
or air filter(s). If the drain tube is restricted, clear it with a‘‘plumbers snake’’ or similar probe device. Ensure that theauxiliary drain port abov
Follow all safety codes. Wear safety glasses and work gloves. Usequenching cloth for unbrazing operations. Have fire extinguisheravailable for all bra
Fig. 25–Typical Heat Pump Operation, Heating ModeC95045STRAINERACCUMULATORCOMPRESSORSTRAINERLCSOUTDOOR COILINDOOR COILABDCCheck ValvesAOpenBClosedCOpe
Fig. 26–Typical Heat Pump Operation, Cooling ModeC95044STRAINERACCUMULATORCOMPRESSORSTRAINERLCSOUTDOOR COILINDOOR COILABDCCheck ValvesAClosedBOpenCClo
Table 8—Troubleshooting—Cooling and HeatingSYMPTOM CAUSE REMEDYCompressor and outdoor fan will not start.Power Failure Call power companyLoss of Charg
START-UP CHECKLIST(REMOVE AND STORE IN JOB FILE)I. PRELIMINARY INFORMATIONModel No ...
Copyright 2006 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231Manufacturer reserves the right to discontinue, or change at any time, speci
Fig. 2—Unit Base Dimensions—50ZH030UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHT CENTER OF GRAVITY IN. (MM)lb kg X Y Z50ZH030 208/230–3–60 254 116 14.0 (
Fig. 3—Unit Base Dimensions—50ZH036–048UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHT CENTER OF GRAVITY IN. (MM)Lb Kg X Y Z50ZH036208/230-3-60,460–3–60277
Fig. 4—Unit Base Dimensions—50ZH060UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHT CENTER OF GRAVITY IN. (MM)Lb Kg X Y Z50ZH060 208/230-3-60, 460-3-60 368
1. Five pieces of flange are shipped on the return-air opening ofthe unit. Remove the flanges from the shipping position (SeeFig. 5). Screws are field
CPVC, or 3/4-in. copper pipe (all field supplied). Do not undersizethe tube. Pitch the drain tube downward at a slope of at least 1 in.for every 10 ft
Table 1 — Physical DataUNIT 50ZH 030 036 042 048 060OPERATING WEIGHT (lbs) 254 277 295 328 368COMPRESSOR TYPE ScrollREFRIGERANT Charge (lb)R-225.8 5.9
PRE-START-UPFailure to observe the following warnings could result inserious injury or death:1. Follow recognized safety practices and wear protective