38AYC
11 SEER Split System
Heat Pump
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol
.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
Before installing, modifying, or servicing system, main elec-
trical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label. Electrical shock can
cause personal injury or death.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit
operation sounds may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate to
capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb
vibration.
5. When passing refrigerant tubes through the wall, seal opening
with RTV or other pliable silicon-based caulk. (See Fig. 2.)
6. Avoid direct tubing contact with water pipes, duct work, floor
joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a
rigid wire or strap which comes in direct contact with tubing.
(See Fig. 2.)
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 2.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
When outdoor unit is connected to factory-approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
indoor unit of the same size when connected by 15 ft of
field-supplied or factory accessory tubing. For proper unit opera-
tion, check refrigerant charge using charging information located
on control box cover and/or in the Check Charge section of this
instruction.
IMPORTANT: Maximum liquid-line size is 3/8-in. OD for all
residential applications including long line.
IMPORTANT: Always install a liquid-line filter drier. Refer to
Product Data Digest for appropriate part number. Obtain filter
drier from your distributor or branch.
INSTALLATION
Step 1—Check Equipment and Job Site
UNPACK UNIT
Move to final location. Remove carton taking care not to damage
unit.
Fig. 1—Model 38AYC
A97005
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 5a 5a
PC 101 Catalog No. 563-852 Printed in U.S.A. Form 38AYC-2SI Pg 1 10-97 Replaces: 38AYC-1SI/38-6SM
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - Heat Pump

38AYC11 SEER Split SystemHeat PumpInstallation and Start-Up InstructionsNOTE: Read the entire instruction manual before starting theinstallation.This

Seite 2 - Dimensions (In.)

WIRING DIAGRAM NOTES:1. CARRIER THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCU-RATE FOR MODEL NUMBERS TSTAT_______.2. WIRING MUST CONFORM TO NEC OR LOCAL CO

Seite 3 - → Table 2—Accessory Usage

Step 13—Check ChargeFactory charge is shown on unit rating plate. To check charge incooling mode, refer to Cooling Only Procedure. To check chargein h

Seite 4 - Fig. 6—Line Power Connections

HEATING CHECK CHART PROCEDURETo check system operation during heating cycle, refer to theHeating Check Chart on outdoor unit. This chart indicates whe

Seite 5

INSPECT EQUIPMENTFile claim with shipping company prior to installation if shipmentis damaged or incomplete. Locate unit rating plate on unit servicep

Seite 6

Step 7—Check Defrost ThermostatCheck defrost thermostat to ensure it is properly located andsecurely attached. There is a liquid header with a brass d

Seite 7

For buried-line applications greater than 36 in., refer to Table 2and Residential Split System Buried-Line Application Guideline.If refrigerant tubes

Seite 8 - Fan Coil and Smart Staging

Use furnace transformer, fan coil transformer, or accessory trans-former for control power, 24-v/40-va minimum.NOTE: Use of available 24-v accessories

Seite 9

Fig. 7—Typical 24-v Circuit Connections using Carrier Model HP Thermostat with Fan Coils and No OutdoorThermostat, 1 Outdoor Thermostat, or 2 Outdoor

Seite 10 - WIRING DIAGRAM NOTES:

Fig. 8—Typical 24-v Circuit Connections using Other HP Thermostats with Fan Coils and No OutdoorThermostat, 1 Outdoor Thermostat, or 2 Outdoor Thermos

Seite 11 - Fig. 12—Defrost Control

Fig. 9—Typical 24-v Circuit Connections using Carrier Model HP Thermostat with Smart Heat and No OutdoorThermostat, 1 Outdoor Thermostat, or Supplemen

Seite 12 - Table 5—Superheat Charging

Fig. 10—Typical 24-v Circuit Connections using Other HP Thermostats with Smart Heat and No OutdoorThermostat, 1 Outdoor Thermostat, or Supplemental He