Table 3A—Electrical Data—50JS
UNIT 50JS
SIZE
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR ODFM IDFM ELECTRIC HEAT POWER SUPPLY
Min Max RLA LRA FLA FLA Nominal KW* FLA MCA Max Fuse or CRCT Breaker MOCP
018 208/230-1-60 187 253 9 48 0.9 1.8
-/-
3.8/5
7.5/10
-/-
18.1/20.8
36.1/41.7
14.0/14.0
24.8/28.3
47.4/54.3
20/20
25/25
50/60
-
-
-
024 208/230-1-60 187 253 12.8 61 0.9 2
-/-
3.8/5
7.5/10
-/-
18.1/20.8
36.1/41.7
18.9/18.9
25.1/28.5
47.6/54.6
25/25
25/30
50/60
-
-
-
030
208/230-1-60 187 253 14.7 82 0.9 2
-/-
3.8/5
7.5/10
11.3/15
-/-
18.1/20.8
36.1/41.7
54.2/62.5
21.3/21.3
25.1/28.5
47.6/54.6
72.8/83.3
25/25
25/30
50/60
-
-
-
-
80/90
208/230-3-60 187 253 9.9 78 0.9 2
-/-
3.8/5
7.5/10
11.3/15
-/-
10.4/12
20.8/24.1
31.3/36.1
15.3/15.3
15.5/17.5
28.6/32.6
44.2/50.2
20/20
20/20
30/35
45/60
-
-
-
-
036
208/230-1-60 187 253 16.8 82 1.5 4.1
-/-
3.8/5
7.5/10
11.3/15
-/-
18.1/20.8
36.1/41.7
54.2/62.5
26.6/26.6
27.7/31.2
50.3/57.2
72.8/83.3
35/35
35/35
60/60
-
-
-
-
80/90
208/230-3-60 187 253 9.9 85 1.5 4.1
-/-
3.8/5
7.5/10
11.3/15
-/-
10.4/12
31.3/36.1
36.1/41.7
18.0/18.0
18.2/20.2
44.2/50.2
47.8/54.7
25/25
25/25
35/40
45/60
-
-
-
-
460-3-60 414 506 5.5 40 0.8 1.9
-/-
5
10
15
-/-
6.0
12.0
18.0
9.6
9.9
17.4
24.9
15
15
20
25
-
-
-
-
042
208/230-1-60 187 253 20.6 115 0.9 3.8
-/-
5
10
15
20
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
30.5/30.5
30.5/30.8
49.9/56.8
72.4/82.9
95.0/108.9
40/40
40/40
50/60
-
-
-
-
-
90.0
100/110
208/230-3-60 187 253 12.4 90 0.9 3.8
-/-
3.8/5
7.5/10
11.3/15
15/19.94
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48
20.2/20.2
20.2/20.2
30.8/34.8
43.8/49.9
56.7/64.7
25/25
25/25
35/35
45/50
-
-
-
-
-
60/70
460-3-60 414 506 6.7 45 0.8 1.8
-/-
5
10
15
15-20
-/-
6.0
12.0
18.0
24.1
11.0
11.0
17.3
24.8
32.3
15
15
20
25
35
-
-
-
-
-
048
208/230-1-60 187 253 24.4 140 1.5 3.5
-/-
3.8/5
7.5/10
11.3/15
15/20
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
35.5/35.5
35.5/35.5
49.5/56.5
72.1/82.5
94.6/108.5
45/45
45/45
50/60
-
-
-
-
-
90.0
100/110
208/230-3-60 187 253 14.1 105 1.5 3.5
-/-
3.8/5
7.5/10
11.3/15
15/19.94
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48.0
22.6/22.6
22.6/22.6
30.4/34.4
43.5/49.5
56.3/64.3
30/30
30/30
35/35
45/50
-
-
-
-
-
60/70
460-3-60 414 506 7.1 53 0.8 1.8
-/-
5
10
15
20
-
6.0
12.0
18.0
24.1
11.5
11.5
17.3
24.8
32.3
15
15
20
25
35
-
-
-
-
-
060
208/230-1-60 187 253 28.8 165 1.5 6.2
-/-
3.8/5
7.5/10
11.3/15
15/20
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
43.7/43.7
43.7/43.7
52.9/59.8
75.4/85.9
98.0/111.9
60/60
60/60
60/60
-
-
-
-
-
90.0
100/125
208/230-3-60 187 253 19.4 125 1.5 6.2
-/-
3.8/5
7.5/10
11.3/15
15/19.94
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48.0
32.0/32.0
32.0/32.0
33.8/37.8
46.8/52.9
59.7/67.7
40/40
40/40
35/40
50/60
-
-
-
-
-
60/70
460-3-60 414 506 8 63 0.8 3.2
-/-
5
10
15
20
-
6.0
12.0
18.0
24.1
14.0
14.0
19.0
26.6
34.1
20
20
20
30
35
-
-
-
-
-
* Heater capacity (KW) based on heater voltage of 208v, 240v, and 480v. If power distribution voltage to unit varies from rated heater voltage, heater KW will vary