Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300012-01 Printed in U.S.A. Form 30XA-7SI Pg 1 1-07 Replaces: New
Book 2
Ta b 5 c
Installation Instructions
Part Numbers 00EFN900003000A, 00EFN900003100A
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Cooler and Economizer Removal. . . . . . . . . . . . . . . . . 4
Remote Cooler and Economizer Installation. . . . . 10
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning
equipment can be hazardous due to system pressures, electrical
components, and equipment location. Only trained, qualified
installers and service technicians should install, start-up, and
service this equipment.
When working on air-conditioning equipment, observe
precautions in the literature and on tags, stickers, and labels
attached to the equipment. Follow all safety codes. Wear safety
glasses and work gloves. Use care in handling equipment.
GENERAL
The remote cooler accessory allows for the indoor reloca-
tion of the cooler on 30XA080-350 units as another means of
freeze protection. When the cooler is located in a heated space,
an anti-freeze solution is not needed and the performance
degradation associated with antifreeze solution can be avoided.
Maximum separation of the 30XA base unit and cooler is
limited to 50 lineal ft (15.25 m) or 75 equivalent ft (22 m) of
piping. For more information, refer to the Carrier Piping De-
sign manual.
The liquid and economizer lines between the exterior-
installed unit and the remote, interior-installed cooler must
have pressure relief devices installed in accordance with
ASHRAE 15 (American Society of Heating, Refrigeration, and
Air Conditioning Engineers) and local codes.
Units to be modified for a remote cooler application must
have the following options:
Factory-installed suction service valve option.
Condenser coil type:
— Aluminum fin and copper tube
— Pre-coat aluminum fin and copper tube
— E-coat aluminum fin and copper tube
— Copper fin and copper tube
— E-coat copper fin and copper tube
NOTE: The microchannel heat exchanger option can NOT use
the remote cooler accessory.
The application is limited to the following constraints:
Operating chilled water temperature is between 40 and 55 F
(4.4 and 12.8 C). When the remote cooler is applied, the
cooler heaters will not function, so it is critical to maintain the
water temperature above the freezing point at all times. If the
water temperature falls below the freezing point, the cooler
does not have protection to keep the water from freezing.
The interior space temperature where the cooler will be
installed must be maintained at a minimum of 50 F (10 C).
Underground refrigerant piping is NOT permitted for this
application.
See Table 1 for accessory package usage and see Table 2 for
accessory package contents. In addition to the parts supplied
with each accessory package, the following material must be
field-supplied:
Refrigerant grade liquid and suction line copper piping for
30XA080-120: circuits A and B and 30XA140-160: circuit
B (length determined by installation). See Tables 3A and 3B
for pipe sizes.
Schedule 40 steel pipe for 30XA140-160: circuit A and
30XA180-350: circuits A and B (length determined by
installation). See Tables 3A and 3B for pipe sizes.
350 psig pressure relief valves and fittings (2 per circuit)
Suction line tubing insulation (length determined by
installation)
Economizer line tubing insulation (length determined by
installation)
1
/
2
in. strain relief (2)
Conduit (length determined by installation)
ASME (American Society of Mechanical Engineers) B16.9
stub end (4 in. [102 mm]), Schedule 40 Steel (one needed
for 30XA140-160, two needed for 30XA180-350)
ASME B16.5 Class 600 pipe flange (4 in. [102 mm]) with
field-modified extra mounting hole (one needed for
30XA260-300, two needed for 325, 350)
Flange mounting hardware
Extra flange gaskets (if necessary)
Table 1 — Accessory Package Usage
Be sure power to equipment is shut off before performing
maintenance or service. Lock out and safety-tag all
disconnects.
The 30XA units use R-134a refrigerant. No other refriger-
ant may be used in this system. Suction tubing design pres-
sure is 220 psig (1517 kPa). Economizer and liquid tubing
design pressure is 350 psig (2413 kPa). Failure to use gage
set, hoses, and recovery systems designed to handle
R-134a refrigerant may result in personal injury and equip-
ment damage. If unsure about equipment, consult the
equipment manufacturer.
30XA UNIT SIZE PACKAGE REQUIRED
080-200 00EFN900003000A
220-350 00EFN900003100A
30XA080-350
Remote Cooler Accessory
60 Hz
Seitenansicht 0
1 2 3 4 5 6 ... 15 16

Inhaltsverzeichnis

Seite 1 - Installation Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Seite 2

10Remote Cooler and Economizers Installa-tion — Install the cooler and economizers in a remotelocation by following this procedure:NOTE: Throughout th

Seite 3 - 15 FT MAX

1112. Using the accessory-supplied M6 screws (3000A or3100A: Item 6), install the accessory-supplied junctionbox (3000A or 3100A: Item 5) at the desir

Seite 4 - INSTALLATION

12Table 6 — Materials Required for Steel Piping Flange Connections LEGEND*Copper connection.UNITSIZECOOLER PIPE FLA

Seite 5

13Table 6 — Materials Required for Steel Piping Flange Connections (cont) LEGENDTable 7 —

Seite 6 - BOTTOM VIEW

14TO 30XABRED.TEE90 DEGREESTR ELLSFROMCOOLER45 DEGREESTR ELLSA 30XA PRESSURE RELIEF VALVES (FIELD- SUPPLIED) ECONOMIZER LINE LIQUID LI

Seite 7

15ASME B16.9STEEL STUB END(FIELD-SUPPLIED)PIPE FLANGE(ACCESSORY-SUPPLIED,SEE TABLE 6)MOUNTINGBRACKETEXISTING FLANGEON FLEXCONNECTOR AT30XA BASE UNIT8

Seite 8 - TOP VIEW

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Seite 9

2Table 2 — Accessory Package ContentsChoose a space that can support the weight of the cooler andeconomizer with service clearances and area for refri

Seite 10

3ECONOMIZERSUCTIONSERVICEVALVE30X A REMOTE COOLERINDOOR LOCAT ION ECONOMIZERSUCTIONSERVICEVALVEREMOTE COOLER30XA INDOOR LOCAT ION 15 FT MAXECONOMIZER

Seite 11

4INSTALLATION1. Inspect package contents for missing or damaged parts.File a claim with the shipping agency if parts aredamaged and notify your local

Seite 12

5Table 4A — Refrigeration Line Sizes (English)Table 4B — Refrigeration Line Sizes (SI)Table 5 — Cooler and Economizer Weights30XA UNIT SIZESUCTION LIN

Seite 13

6SIDE VIEWBOTTOM VIEW13/16(20)1/2(13)10-23/32(272)118-13/16(3017)52-1/4(1327)52-1/4(1327)23-1/32(585)15-5/16(389)64(1625)15-5/16(389)45-1/4(1149)15-5/

Seite 14 - ECONOMIZER

7SIDE VIEWBOTTOM VIEW1/2(13)13/16(20)11-3/16(284)119-9/32(3030)52-1/4(1327)25-1/16(636)52-1/4(1327)18-3/8(466)57(1448)18-3/8(466)52-1/4(1327)18-3/8(46

Seite 15

8SIDE VIEW END VIEWTOP VIEW30-3/8(770)22-7/8(581)23-1/2(598)7-7/8(200)2 x Ø 7/16 (11)29-3/8(746)6-1/2(166)7/16(12)5/8(17)7/16(11)7/8(21)7/16(11)7/8(21

Seite 16 - Ta b 5 c

9Fig. 6 — Typical Cooler Piping-Cooler Side View (30XA140, 160 Shown)NOTES:1. Circuit A uses steel suction piping.2. Circuit B uses copper suction pip