ERVC CSVB1100, ERVC CSHB1100HRVCCSVB1100, HRV CCSHB1100Energy / Heat Recovery VentilatorInstallation InstructionsNOTE: Read the entire instruction man
10If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where on theunit
11Table 6 – Temperature / Ohm RelationshipTEMP. (°F/°C) RESISTANCE (OHMS)--- 9 / --- 2 3 78330--- 8 / --- 2 2 74610--- 6 / --- 2 1 71100--- 4 / --- 2
12CONNECTION DIAGRAMLine voltage factory wiringClass 2 low voltage factory wiringClass 2 low voltage field wiringM1A1T1R1Field wiringremote control(se
13120V, 60Hz Neutral120V, 60Hz LineCPUK2K4K5J5-2J10-1J10-2Exhaust fan motorSupply fan motorJ5-1J5-3J7-2J7-1J4-1J4-3J6-2J6-1K1K3K2J9-1J9-2J9-3J4-2J9-4E
14These products earned the ENERGY STAR®by meeting strictenergy efficiency guidelines set byNatural Resources Canada andthe US EPA. They meet ENERGYST
2INTRODUCTIONThe Energy/Heat Recovery Ventilator (ERV/HRV) is used toexchange indoor stale air with outside fresh air. The unit isequipped with a spec
3UNIT INSTALLATIONUNIT DAMAGE HAZARDFailure to follow this caution may result in equipmentdamage or improper operation.Do not install ERV/HRV in a cor
4Connect Ducts to ERV/HRVPROPERTY DAMAGE HAZARDFailure to follow this caution may result in minor propertydamage from sweating duct or loss of unit ef
5between wall control and ERV/HRV connector following colorcode. (See Fig. 5 and 10.) Replace top cover assembly.NOTE: ERV/HRV wall control and circui
6OPERATING THE ERV/HRV WITHTHE INFINITY CONTROLThe ventilator has four settings in heating mode and three settingsin cooling mode.Heating:AUTO -- the
7BALANCING ERV/HRVBalancing intake and exhaust airflow is very important for propersystem operation and optimum performance when applying anERV/HRV. U
8VENTILATION EVALUATIONUNIT DAMAGE HAZARDFailure to follow this caution may result in reduced unitefficiency, capacity or unit life.DO NOT use HRV dur
9NOTE: The core should only be serviced when outdoortemperature is 60°Fto75°F(16°Cto24°C) and it is dry.UNIT COMPONENT DAMAGE HAZARDFailure to follow