
Table 2 - Two-Stage Sequence of Operations
Inducer Pre-Purge Period: When the inducer motor comes up on high speed, the pressure switch closes, and the Infinity _ ignition control
on the furnace board begins a 15 sec pre-purge period. If the pressure switch fails to remain closed, the inducer will remain running. After
the pressure switch recloses, the Infinity ignition control will begin a 15 sec pre-purge period.
Trial-for-Ignition Sequence: The spark igniter will spark for 3 sec, the main gas valve relay contact closes to energize the gas valve on low
stage. After 5 sec, the igniter is de-energized and a 2-sec flame-proving period begins.
NOTE: The unit always lights on high speed inducer and low stage gas valve operation.
Flame-Proving: When the burner flame is proved at the flame-proving sensor, the furnace control determines what heating stage to run
based on feedback from the User Interface (UI). If the UI is asking for low stage gas heat, the ignition control will change the inducer speed
to low speed and keep the gas valve energized on low stage. If the UI is asking for high stage gas heat, the ignition control will maintain
running the inducer on high speed and energize the gas valve's high stage relay to increase gas flow.
Table 3 - Two-Stage Rated Heating Input, Propane Gas (2001-6000 ft [610-1829 m] Altitude)
RATED HEATING INPUT PROPANE(BTU/HR)
NAMEPLATE INPUT, HIGH STAGE (BTU/HR)
40,000
60,000
90,000
115,000
130,000
HIGH STAGE
38,000
57,000
79,000
103,000
116,000
LOW STAGE
26,000
39,000
58,500
75,000
84,500
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal
iniury and/or property damage.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections. A fire or
explosion may result causing property damage, personal
iniury of loss of life,
MANIFOLD PIPE PLUG
099019
Fig. 5 - Two-Stage Burner Assembly
BURNER FLAME
(Blue in appearance)
BURNER
MANIFOLD
Fig. 6 - Monoport Burner
C99021
IMPORTANT: Restart unit and leak check all gas connections
including the main service connection, gas valve, gas spuds, and
manifold pipe plug. All leaks must be repaired before firing unit.
32. Fire unit and verify proper ignition and proper sequence of
operation (Table 2). See Table 4 for proper low stage and
high stage manifold pressure settings for your unit. Adjust
the gas valve setting for high and low stages by turning the
plastic adjustment screws clockwise to increase pressure and
counter-clockwise to decrease pressure for the respective
stages. Refer to Table 3 for required rated heating input
rates. Replace regulator cover screws when finished (see
Fig. 3).
33. With control access panel removed, observe unit heating
operation in both low stage operation and high stage opera-
tion. Watch burner flames to see if they are blue in appear-
ance, and that the flames are approximately the same for
each burner (see Fig. 6).
34. Turn off unit, remove pressure manometer and replace the
1/8 in. pipe fitting on the gas manifold (see Fig. 5).
35. Attach warning label (P/N 48DU500076) to visible side of
gas valve.
36. Attach conversion label (P/N 48VL500285) above unit
rating plate on exterior of unit.
37. Attach completed conversion responsibility label (see Fig.
8, P/N 48VL500286) inside service access panel.
Kommentare zu diesen Handbüchern