Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903 Catalog No. 563-020 Printed in U.S.A. Form 30G,H/38A-2SI Pg 1 9-00 Replaces: 30G,H/38A-1SI
Book 1 2
Ta b 3 a 5 c
Installation Instructions
30GA900161 (60 Hz — 115-v Control)
30GA900171 (50 or 60 Hz — 230-v Control)
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION IN
30GN,GT,GTN,GTR,GUN,GUR,HK,HL
. . . . . . . . . 2-8
Step 1 — Examine Package Contents
. . . . . . . . . . . . 2
Step 2 — Install Piping
. . . . . . . . . . . . . . . . . . . . . . . . . . . 2
30GN,GT,GTN,GTR,GUN,GUR040-420 UNITS
30GTN015-035, 30HK040-060, AND
30HL050,060 UNITS
Step 3 — Dehydrate and Recharge Unit
. . . . . . . . . . 3
Step 4 — Install Control Wiring
. . . . . . . . . . . . . . . . . . . 4
OPERATION AND ADJUSTMENT
. . . . . . . . . . . . . . .8-11
30GN Units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
30GT Units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
All
Comfort
Link™ Units
. . . . . . . . . . . . . . . . . . . . . . . . . 11
INSTALLATION IN 38AKS, AH/INDOOR FAN COIL
(CONSTANT VOLUME/SPLIT SYSTEM
COMBINATION)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-15
Step 1 — Install Piping
. . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 2 — Install Control Wring
. . . . . . . . . . . . . . . . . . 12
Step 3 — Restore Refrigerant Charge
. . . . . . . . . . . 13
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical com-
ponents, and equipment location.
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When working on air-conditioning equipment, observe pre-
cautions in the literature and on tags, stickers, and labels at-
tached to the equipment.
Follow all safety codes. Wear safety glasses and work
gloves. Use care in handling equipment.
INTRODUCTION
These instructions cover field installation of the accessory hot
gas bypass (HGBP) valve and solenoid pilot valve on specific
models. These models include the 30GT Flotronic™ chillers
and 30GN Flotronic II chillers in sizes 040-420. Also included
are all 30GTN,GTR,GUN,GUR040-420, 30GTN015-035 and
30HK,HL040-060 ComfortLink chillers. See Table 1.
On Flotronic chillers (30GT) with either no unloaders or
2 unloaders, the accessory hot gas bypass must be added to
both circuits because of an automatic lead-lag feature. On
ComfortLink chillers (30GTN,GTR,GUN,GUR040-070 sizes),
the addition of a compressor unloader solenoid coil must also be
added to compressor B1 to use the configurable lead-lag feature.
On 30GN,GT,GTN,GTR,GUN,GUR130-210 sizes, 2 hot
gas bypass packages must be installed, one on each circuit. On
30GN,GT,GTN,GTR,GUN,GUR230-420 sizes, 4 hot gas by-
pass packages must be installed, 2 on each unit module (Mod-
ules A and B).
For 30GT units, hot gas bypass will be activated only if the
lead compressor on a circuit is active. For 30GN,
30GTN,GTR, 30GUN,GUR and 30HK,HL units, hot gas by-
pass will be activated only if the lead compressor on a circuit is
both active and unloaded.
NOTE: The lead compressor in circuit A is compressor A1.
The lead compressor in circuit B is compressor B1. For loca-
tion of lead compressor, refer to component arrangement in
wiring schematic on unit.
Table 1 — Accessory Application
Be sure power to equipment is shut off before performing
maintenance or service.
IMPORTANT: When removing refrigerant, use an
approved refrigerant recovery device. Do not vent refrig-
erant into the atmosphere.
IMPORTANT: The following 2 combinations ARE NOT
ALLOWED on 30GN,GT,GTN,GTR,GUN,GUR230-
420 units.
Two unloaders and hot gas bypass on one circuit.
Four compressors, 1 unloader, and hot gas bypass
on one circuit.
UNITS
UNIT
TYPE
CONTROL
VOLTAGE
HOT GAS
PART N O.
30GA900-
30HK040-060
30HL050,060
50/60 Hz 115 v 161
30GTN015-035
60 Hz
60 Hz
115 v
230 v
161
171
30GTN020-030
50 Hz 230 v 171
30GN,GT,GTN,
GTR,GUN,
GUR040-420
60 Hz
60 Hz
50 Hz
115 v
230 v
230 v
161
171
171
38AK,AKS
60 Hz
60 Hz
50 Hz
115 v
230 v
230 v
161
171
171
38AH
60 Hz
60 Hz
50 Hz
115 v
230 v
230 v
161
171
171
30GN,GT,GTN,GTR,GUN,GUR,HK,HL
38AH,AKS
Accessory Hot Gas Bypass Packages
50/60 Hz
Seitenansicht 0
1 2 3 4 5 6 ... 15 16

Inhaltsverzeichnis

Seite 1 - Installation Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Seite 2 - Step 2 — Install Piping

10Fig. 10 — 30HK,HL with ComfortLink™ ControlsFig. 11 — 30HK,HL Hot Gas Bypass Field WiringFig. 12 — 30GTN015-035 Hot Gas Bypass Field Wiring

Seite 3 - CIRCUIT B SIDE

1130GT Units — With a call for the first compressor, theHGBPR (hot gas bypass relay) is energized, completing a cir-cuit to the appropriate TDR-HG (ti

Seite 4 - Field Tube (Copper)

12Step 2 — Install Control Wiring (See Fig. 14-17)38AKS028-0441. Install a field-supplied relay with a 24-v coil(HN61KK324 suggested) and normally clo

Seite 5

13NOTE: This relay is identified in Fig. 17 as HGR (hot gasrelay).2. COIL WIRINGConnect a field-supplied wire between TB4-2 andHGR-1 (L1 side of coil)

Seite 6

14TB3213CR1LLSV-11TB345HGRHOT GASSOLENOID VALVE313HGRLLSV-2TB3TB3513SDR2LLS-A17TB345HGRHOT GASSOLENOID VALVE313HGRTB3LINE 255LINE 25764SDR2

Seite 7

15TB3513SDR2LLS-A17TB345HGRHOT GASSOLENOID VALVE213HGRTB4LINE 315/350 (044-084) 340/345 (094,104)31SDR48TB3LINE 224 (044-084) 240 (094

Seite 8 - 30GN Units —

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Seite 9 - 30GTN,GTR,GUN,GUR040-420

2INSTALLATION IN 30GN,GT,GTN,GTR,GUN,GUR,HK,HL CHILLERSStep 1 — Examine Package Contents — Pack-age includes hot gas bypass valve, solenoid pilot valv

Seite 10

3Solenoid Pilot Valve — Install the solenoid pilot valve in theexternal equalizer line of the bypass valve. The solenoid valvehas a 3/8-in. ODF inlet

Seite 11

4Step 4 — Install Control WiringWires between field-installed components and unit controlbox must be enclosed in field-supplied conduit. Follow all lo

Seite 12 - Thermostatic Expansion Valve

530GN UNIT: 040-110; 230B-315B MODULES30GN UNIT: 130-210; 230A-315A, 330A/B-420A/B MODULES30GT UNIT: 040-110; 230B-315B MODULES30GT UNIT: 130-210; 230

Seite 13 - TROUBLESHOOTING

6 LEGENDFig. 5 — 30GN, 20-v Hot Gas Bypass WiringCOMM —CommunicationHGBPR —Hot Gas Bypass Relay (Field Supplied)PWR —Powe

Seite 14

730GT Units — All control box internal wiring is suppliedfrom the factory in a harness assembly. Connect the coil ofHGBPR-A in series between TB5-3 an

Seite 15

830GTN,GTR,GUN,GUR040-420 Units — Open the controlbox door. Locate terminal block TB5. See Fig. 8. Using field-supplied wiring, conduit and fittings w

Seite 16 - Ta b 3 a 5 c

930GTN,GTR,GUN,GUR040-110; 230B-315B MODULES(080-110, 230B-315B SHOWN)30GTN,GTR,GUN,GUR130-210; 230A-315A; 330A/B-420A/B MODULESFig. 8 — Hot Gas Bypas