Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9
10Fig. 10 — 30HK,HL with ComfortLink™ ControlsFig. 11 — 30HK,HL Hot Gas Bypass Field WiringFig. 12 — 30GTN015-035 Hot Gas Bypass Field Wiring
1130GT Units — With a call for the first compressor, theHGBPR (hot gas bypass relay) is energized, completing a cir-cuit to the appropriate TDR-HG (ti
12Step 2 — Install Control Wiring (See Fig. 14-17)38AKS028-0441. Install a field-supplied relay with a 24-v coil(HN61KK324 suggested) and normally clo
13NOTE: This relay is identified in Fig. 17 as HGR (hot gasrelay).2. COIL WIRINGConnect a field-supplied wire between TB4-2 andHGR-1 (L1 side of coil)
14TB3213CR1LLSV-11TB345HGRHOT GASSOLENOID VALVE313HGRLLSV-2TB3TB3513SDR2LLS-A17TB345HGRHOT GASSOLENOID VALVE313HGRTB3LINE 255LINE 25764SDR2
15TB3513SDR2LLS-A17TB345HGRHOT GASSOLENOID VALVE213HGRTB4LINE 315/350 (044-084) 340/345 (094,104)31SDR48TB3LINE 224 (044-084) 240 (094
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9
2INSTALLATION IN 30GN,GT,GTN,GTR,GUN,GUR,HK,HL CHILLERSStep 1 — Examine Package Contents — Pack-age includes hot gas bypass valve, solenoid pilot valv
3Solenoid Pilot Valve — Install the solenoid pilot valve in theexternal equalizer line of the bypass valve. The solenoid valvehas a 3/8-in. ODF inlet
4Step 4 — Install Control WiringWires between field-installed components and unit controlbox must be enclosed in field-supplied conduit. Follow all lo
530GN UNIT: 040-110; 230B-315B MODULES30GN UNIT: 130-210; 230A-315A, 330A/B-420A/B MODULES30GT UNIT: 040-110; 230B-315B MODULES30GT UNIT: 130-210; 230
6 LEGENDFig. 5 — 30GN, 20-v Hot Gas Bypass WiringCOMM —CommunicationHGBPR —Hot Gas Bypass Relay (Field Supplied)PWR —Powe
730GT Units — All control box internal wiring is suppliedfrom the factory in a harness assembly. Connect the coil ofHGBPR-A in series between TB5-3 an
830GTN,GTR,GUN,GUR040-420 Units — Open the controlbox door. Locate terminal block TB5. See Fig. 8. Using field-supplied wiring, conduit and fittings w
930GTN,GTR,GUN,GUR040-110; 230B-315B MODULES(080-110, 230B-315B SHOWN)30GTN,GTR,GUN,GUR130-210; 230A-315A; 330A/B-420A/B MODULESFig. 8 — Hot Gas Bypas