Carrier Performance 48VR-A Bedienerhandbuch Seite 29

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 58
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 28
29
Table 8 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
Orange = Med---High Speed
Red=MedSpeed
Pink = Med---Low Speed
Blue = Low Speed
Selection of Proper Fan Speeds for Operation
Modes:
NOTE: All models are factory--shipped for nominal high stage
and low stage cooling airflow operation at minimum external static
pressure. Many models are factory--shipped for nominal high stage
and/or low stage gas heating airflow at minimum external static
pressure. Table 10 provides airflow data for higher external static
pressures.
Low Stage Gas Heating: Table 10 shows the suitability of each
speed for a given external static pressure for low stage gas heating.
Any speed/static combination that is outside the rise range is
marked “NA” and must not be used. The unit must operate within
the low stage gas heat rise range printed on the rating plate.
Connect the chosen fan speed wire to “LO HEAT connection on
theIGCBoard(seeFig.18).
High Stage Gas Heating: Table 10 shows the suitability of each
speed for a given external static pressure for high stage gas heating.
Any speed/static combination that is outside the rise range is
marked “NA” and must not be used. The unit must operate within
the high stage gas heat rise range printed on the rating plate.
Connect the chosen fan speed wire to “HI HEAT” connection on
theIGCBoard(seeFig.18).
Low Stage Cooling/Heat Pump: Using Tables 11, 12, and 13,
and the nominal airflow for low stage cooling (Table 1) find the
external static pressure drops for wet coil, economizer, and filter,
and add them to dry coil measured on the system. Using this total
static pressure, use Table 10 to find the airflows available at the
total static pressure. Connect the chosen fan speed wire to “LO
COOL” connection on the IGC Board (see Fig. 18).
High Stage Cooling/Heat Pump:Using Tables 11, 12, and 13,
find the external static pressure drops for wet coil, economizer, and
filter, and add them to dry coil measured on the system. Using this
total static pressure, use Table 10 to find the airflows available at
the total static pressure. The speed chosen must provide airflow of
between 350 to 450 CFM per ton of cooling. Connect the chosen
fan speed wire to “HI COOL connection on the IGC Board (See
Fig. 18).
High Stage Enhanced Dehumidification Cooling: Using the
total static pressure for selecting the high stage cooling speed, use
Table 10 to find lower speed/airflows available at that total static
pressure. All airflows highlighted in Table 10 are acceptable for
Dehum speed. The speed chosen must provide airflow of between
320 to 400 CFM per ton of cooling. Connect the chosen fan speed
wire to “DHUM” connection on the IGC Board (see Fig. 18).
To activate the high stage enhanced dehumidification cooling
mode, the shunt jumper in Fig. 18 must be moved from the No DH
to DH selection (See Fig. 18, close up).
Continuous Fan (All models): Continuous fan speed is the same
speed as Low Stage Cooling.
Using the Same Fan Speed for More than One Mode: Some fan
speeds are ideal for more than one mode of operation. It is
permissible to use a field--supplied jumper wire to connect one
speed tap wire to two or more speed connections on the ignition
board (IGC). Jumper wires must use 18 AWG wire with at least
2/64” insulation.
Cooling Sequence of Operation
a. Continuous Fan
(1.) Thermostat closes circuit R to G energizing the
blower motor for continuous fan. The indoor fan is
energized on low speed.
b. Cooling Mode
(1.) Low Stage: Thermostat closes R to G, R to Y1
and R to O. The compressor and indoor fan are
energized on low speed. The outdoor fan is also
energized.
(2.) High Stage: Thermostat closes R to G, R to Y1, R
to Y2 and R to O. The compressor and indoor fan
are energized on high speed. The outdoor fan is
also energized.
c. Heat Pump Mode
(1.) Low Stage: Thermostat closes R to G, R to Y1.
The compressor and indoor fan are energized on
low speed. The outdoor fan is also energized.
(2.) High Stage: Thermostat closes R to G, R to Y1, R
to Y2. The compressor and indoor fan are ener-
gized on high speed. The outdoor fan is also ener-
gized.
d. Defrost Mode
(1.) Outdoor Fan is disabled, thermostat closes R to O
and R to W1. Low stage gas heat tempers the leav-
ing air. When defrost is complete, unit will return
to heating mode. If room thermostat is satisfied
during defrost, unit will shut down and restart in
defrost on next call for heat.
Step 4 Defrost Control
Quiet Shift
Quiet Shift is a field--selectable defrost mode, which will eliminate
occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3
(on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is
initiated, the following sequence of operation will occur. Reversing
valve will energize, outdoor fan will turn off, compressor will turn
off for 30 sec and then turn back on to complete defrost. At the
start of heating after conclusion of defrost reversing valve will
de--energize, compressor will turn off for another 30 sec, and the
outdoor fan will stay off for 40 sec, before starting in the Heating
mode.
Defrost
The defrost control is a time/temperature control which includes a
field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at
60 minutes). To initiate a forced defrost, two options are available
depending on the status of the defrost thermostat.
48VR-- A
Seitenansicht 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 57 58

Kommentare zu diesen Handbüchern

Keine Kommentare