TROUBLESHOOTING
Table 6—Indicator Lamps Troubleshooting
LAMPS STATUS INDICATION CORRECTIVE ACTION
POWER flashes 10 seconds after A/C
start-up (with or without other signal lamps)
Communication problem.
• Check connection between indoor
(TAC-440) and outdoor (TAC-420) units (for TAC-400, ANC).
• Check connection between TAC-444 and TAC-460 (for TAC-404).
POWER, COMPRES. and PRESSURE
lamps flash.
Thermistor failure.
• Check TH-1 for correct resistance.
• Check for proper connection between TH-1 and TAC-444.
• Replace TH-1 if necessary.
POWER, COMPRES. and IMPEDANCE
lamps flash.
Thermistor failure.
• Check TH-2 for correct resistance.
• Check for proper connection between TH-2 and TAC-444.
• Replace TH-2 if necessary.
POWER lamp flashes and PRESSURE
is lit, AIR CON is Off.
Low Pressure
• Check if the filters are clean.
• Check TH-1 and TH-2 for correct resistance.
• Check cooling system for normal operation.
POWER and PRESSURE lamps flash,
AIR CON is Off.
High Pressure.
• In Heat mode: Check if the evaporator is blocked. (Check if filters
are clean.)
• Check TH-2 (in Heating mode) or TH-3 (in Cool mode) for correct
resistance.
• Check cooling system for normal operation.
FILTER is lit. Filter cleaning. • Clean all filters.
POWER, IMPEDANCE lamps flash,
COMPRES. is lit.
Low voltage.
• Check power supply voltage.
• Check electrical connections.
• Replace TAC-444.
POWER lamp flashes, IMPEDANCE
and COMPRES. lamps lit. AIR CON
lamp flashes after A/C start-up.
Voltage failure at start-up.
• Check power supply voltage.
• Check electrical connections.
• Replace TAC-444.
POWER lamp flashes, IMPEDANCE
and COMPRES. are lit before A/C startup.
High Voltage.
• Check power supply voltage.
• Check electrical connections.
• Replace TAC-444.
POWER lamp flashes, IMPEDANCE and
COMPRES. are lit. AIR CON is lit
after A/C startup.
High voltage during compressor operation.
• Check power supply voltage.
• Check electrical connections.
• Replace TAC-444.