Software Revs 3,5,6,8,10, 12 Infinity /Evolution Troubleshooting (Rev. 2)
10-12-2006
21
Troubleshooting Communication Bus
Connect UI to indoor
unit at the indoor unit.
CAN NOT FIND INDOOR UNIT
Disconnect O.D. unit
and all other devices
on ABCD bus except
indoor unit and UI.
Cycle system power.
Indoor
unit
f
ou
n
d?
Indoor
unit
f
ou
n
d?
Try
another
U
I
?
Measure voltage on ABC
terminals at indoor unit (see
Table-1) Possible indoor unit
problem.
Check wiring to UI
mounting location.
NO
NO
NO
YES
Reconnect one
device at a time to
ABCD bus.
YES
Device
found?
Check device
wiring.
Wiring
OK?
Correct
wiring and
reinstall
system.
Measure
voltage on
ABC
terminals at
device (see
Table- 1)
Possible
device
problem.
YES
NO
NO
YES
YES