42PQV/38VBH
1:1 inverter Heat pump system
ENGLISH
GB - 1
For operation and maintenance instructions of this unit as well as installation
instructions, refer to owner’s manuals.
Contents
Page
General information ....................................................................................................................... 2
Dimensions and weight ................................................................................................................. 3
Connections................................................................................................................................... 3
Minimum clearances and operating limits ..................................................................................... 4
Material supplied and system charge ............................................................................................ 5
Choosing the installation site......................................................................................................... 6
Warnings: avoid ............................................................................................................................. 7/8
Installation for indoor unit .............................................................................................................. 9/10
Refrigerant connections ................................................................................................................ 11/13
Check............................................................................................................................................. 14
Electrical connection for indoor unit .............................................................................................. 15
Electrical connection for outdoor unit ............................................................................................ 16
Electrical connection ..................................................................................................................... 17
Electrical data ................................................................................................................................17
Pump down and refrigerant cycle .................................................................................................. 18
Operating test address selector and fault code............................................................................. 19
Unit configuration, remote configuration, guide for owner and accessories ................................. 20
Maintenance and Troubleshooting ................................................................................................ 21
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A – QUICK REFERENCE GUIDE
• R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical
position with the valve at the top.
• R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device
in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
• R-410A, as other HFCs, is only compatible with oils selected by the compressor manufacturer.
• A vacuum pump is not enough to remove moisture from oil.
• Oils absorb moisture rapidly. Do not expose oil to atmosphere.
• Never open system to atmosphere while it is under vacuum.
• When the system must be opened for service, break vacuum with dry nitrogen.
• Do not vent R-410A into the atmosphere.
• Use only Carrier matching indoor units and outdoor units (Table I).
Indoor unit Outdoor unit Power supply Oil type Quanty cc
42PQV009 38VBH009
220-240V, 50/60Hz
PVE 440
42PQV012 38VBH012 PVE 550
Table I