Models 28VQ,HQ coils and 40FS heaters are for
use in cooling-only and/or cooling and electric
heating systems. The 28VQ and HQ coils are also
for use in heat pump systems with 38HQ or 40FQ
electric heaters. Model 28TQ coil is for installation
in 38TQ 2-speed heat pump systems. The 28QX coil
is for solar-assisted heat pump systems. The 28VH
coil application is with Model 40FS075 only.
Fan section, coil and electric heater are tested
and approved for installation in unconditioned
space per ARI Standard (80 F db, 75 F wb indoor
temperature; 80 F db outdoor temperature). Insu
late supply and return air ductwork in uncondi
tioned space. If conditions exceed the ARI Stand
ard, additional insulation with vapor barrier may
be required for the unit.
Fan Sections 40FS can be positioned to discharge
air upward (upflow), horizontally, or downward
^(downflow), except for sizes 075, 120 which cannot
be used in downflow applications, and are suitable
for “Attic-Type” installations.
The 28 Series Coils are approved as draw-thru
(airflow) units only with the 40FS fan section. Install
coils in draw-thru position; heater in blow-thru
position. Therefore, coil must be attached to air inlet
end of fan section. As indicated in Table 3, per
missible coil airflow position(s) in system are:
28TQ upflow, downflow or horizontal; 28VQ
upflow or downflow; 28HQ horizontal; 28QX
upflow or horizontal; 28VH002 horizontal or
^upflow with 40FS075 only, upflow with 40FS120
only.
Assembly of coils to 40FS fan section, electric
heater and filter section is described in this booklet.
For further coil information, see 28 Series installa
tion data.
COIL CONDENSATE DRAINAGE (for any unit
assembly installed above an occupied or usable
space) In addition to normal condensate drain
line connection, install an auxiliary condensate pan
under entire unit assembly. Route drain line to any
drain that is visible to occupant. In 28 VH coil appli
cations, only the drain pan needed should be used.
See 28VH Installation Instructions.
Under prolonged high humidity conditions, elimi
nator plates may be required on downflow applica
tions. Horizontal coil installation may also require
special condensate removal methods. See Coil In
stallation Data.
Accessory Electric Heater is used with 40FS,
208/230-volt fan section. See Electrical Data and
Wiring table for fan section/electric heater usage.
Use electric heater as a blow-thru unit only by
attaching heater to air discharge end of 40FS fan
section in any of the 3 positions. Electric heater
has both heating and cooling controls including a
40-va or 60-va control circuit transformer, indoor
fan relay and low-voltage terminal strip.
MODELS 40FS916320 AND 40FS916500EH,
GM AND HV These heaters are approved for
downflow usage but require the use of adapters
(downflow support angles) to support fan section
weight. See Installation, Heating Unit Assembly.
Filter Section is shipped taped to air inlet end of
fan section. Filter section includes a reversible
filter rack with 5/8-in. duct connection flanges. On
most unit assemblies the filter section can be
attached to unit with flanges exposed or turned over
so flanges are inside unit. The permanent one-in.
filter media pulls out (Fig. 1) for easy removal and
cleaning.
Cooling Control Kit is an accessory for 40FS,
208/230-volt fan sections used in cooling-only in
stallations. The kit contains a 40-va transformer, fan
deck filler panels, indoor fan relay and low-voltage
terminal strip. See Fig. 11, and cooling control kit
installation on page 9. Because accessory electric
heaters come equipped with cooling controls listed
above (plus required heating controls), a cooling
control kit is not required when electric heater is
used. An accessory humidity control kit is required
for use in 28TQ 2-speed installations. See Step 7
and Fig. 12.
INSTALLATION
Step 1 — Inspect Equipment File claim with
shipping company if shipment is damaged or
incomplete.
Step 2 Determine Position of Unit by Air
flow Direction — See Table 3 and Fig. 2, 3, 4 and
5. Ensure access panels on all units face front before
and after unit assembly.
Step 3 Assemble Required Unit Follow
assembly procedure below for required unit. On
downflow unit assemblies, loosen or remove fan
motor mounting bolts and rotate fan motor so
oiling holes are a minimum of 45° above horizontal
center line of motor.
Fasteners for assembling units are shipped in a
bag inside of fan section or inside electric heater
enclosure. Use the no. 10 serrated hex head sheet
metal screws (or equivalent) provided, where indi
cated in unit assembly instructions below, to ensure
proper electrical ground continuity.
( .\l NON: \ll coil'« iiiii'l be applied draw-ihru
and l1e:ller.^ blow-ihiii v\heii eombining
HEATING UNIT ASSEMBLY (Fig. 2)
Electric Heater Models except 40FS916320.
40FS916500EH. GM and HV. and 40FS916500LW
and PA when used with fan sections 40FS075.
-»40FS120. 40FS200 and 40FS220 Position fan
section for upflow air direction. (Accessory flange
deck40FS900391 or40FS900401 required.) Setelec-
tric heater on air discharge end of fan section.
Attach heater to fan section with 5 no. 8-32 self
threading screws provided. Clearance holes for
screws are provided on each side (2) and hack (1) of
fan section and engagement holes on heater.
Electric Heater Models 40FS916320. 40FS916330
and 40FS9165Q0EH. GM and HV Position fan
section for upflow air direction. Mount heater on
fan section supply air duct connection flanges, and
attach with 4 sheet metal screws. Four clearance
holes for screws, provided on heater cabinet, can
be used as template for drilling engagement holes
in duct flanges as required. See Fig. 3. Assembly
may be aided by first removing top flange deck
from fan section (2 screws hold flange deck in place).
Assembled heater and flange deck can then be
resecured to fan section. Reposition plug buttons