Product Data40MBFQFloor Console Ductless SystemSizes 09 to 12NOTE: Image for illustration purposes only. Actual model maydiffer slightly.INDUSTRY LEAD
10FAN AND MOTOR SPECIFICATIONSSYSTEM SIZE9 12(208-230V) (208-230V)Indoor fanmaterial AS ASType LX-370*80*8-7JN LX-370*80*8-7JNDiameter inch 14.6 14.6H
11WIRING DIAGRAMXS1-XS5XP1-XP5CN1-CN20RT2 RT1XT1M1FAN 4-WAY TERMINALROOM TEMPERATUREPIPE TEMPERATURECONNECTORSCONNECTORSP.C BOARD SOCKETSWIRING DIAGR
12GUIDE SPECIFICATIONSINDOOR WALL−MOUNTED FLOOR CONSOLE DUCTLESS UNITSSize Range: 3/4 to 1 Ton Nominal Cooling and Heating CapacityModel Number: 40MBF
2LOW SOUND LEVELSWhen noise is a concern, the ductless systems are the answer. Theindoor units are whisper quiet. There are no compressors indoors,eit
3MODEL NUMBER NOMENCLATUREQF-SYSTEM TYPEQ = HEAT PUMPINDOOR FAN COIL TYPEF= FLOOR CONSOLENOT USEDINDOOR UNIT40 MB 30940= FAN COIL UNITMB = MODELVOLTAG
4STANDARD FEATURES AND ACCESSORIESEase Of InstallationMounting Brackets SLow Voltage Controls SComfort FeaturesMicroprocessor Controls SWired Remote C
5DIMENSIONS − INDOOR0.63(16)Drain pipe7.68(195)Hanging armUnit: in (mm)27.56(700)23.62(600)8.27(210)Fig. 2 – Indoor UnitUNIT SIZE 9 12Depth in (mm) 8.
6CLEARANCES − INDOORFig. 3 – Indoor Unit ClearanceSPECIFICATIONSHeat PumpSystemSize 9 12Indoor Model 40MBFQ09---3 40MBFQ12---3ElectricalVoltage, Phase
7APPLICATION DATAUNIT SELECTIONSelect equipment to either match or is slightly less than theanticipated peak load. This provides better humidity contr
8WIRINGAll wires must be sized per NEC (National Electrical Code) orCEC (Canadian Electrical Code) and local codes. Use the ElectricalData table MCA (
9AIR FLOW DATASYSTEM SIZE 9 12Indoor (CFM)High 280 280Medium 250 250Low 220 220SOUND PRESSURESYSTEM SIZE 9 12Cooling operation Indoor SoundPressuredBa