Table 5 — Electrical Data
LEGEND
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
3. The 575-v units are CSA only.
4. the 380 v, 60 Hz units and all 50 Hz units are
not
UL or CSA
listed.
UNIT
38
NOMINAL VOLTAGE
(V-Ph-Hz)
VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY
MIN MAX RLA LRA FLA MCA MOCP
AK007
208/230-3-60 187 254 21.8 158 1.9 30.1 40
460-3-60 414 508 10.0 79 1.0 13.6 20
575-3-60 518 632 9.0 65 1.9 14.1 20
220-3-50 198 242 21.8 158 1.0 28.8 35
400-3-50 360 440 10.0 79 1.0 14.0 20
AK008
208/230-3-60 187 254 28.8 195 3.8 39.8 50
460-3-60 414 508 14.7 95 1.9 20.3 25
575-3-60 518 632 10.8 80 1.9 15.4 20
220-3-50 198 242 28.8 195 1.5 37.5 45
400-3-50 360 440 14.7 95 1.5 19.9 25
AK012
208/230-3-60 187 254 37.8 239 3.8 39.8 20
460-3-60 414 508 17.2 125 2.2 20.3 30
575-3-60 518 632 14.3 90 1.9 15.4 25
220-3-50 198 242 37.8 239 1.4 48.8 60
400-3-50 360 440 17.2 125 1.4 23.0 30
AKS008
208/230-3-60 187 254 31.5 160 3.1 42.5 50
380-3-60 342 418 19.0 75 2.2 26.0 35
460-3-60 414 508 15.7 80 1.4 21.0 25
575-3-60 518 632 12.6 64 1.4 17.2 20
220-3-50 198 253 31.5 160 1.4 42.5 50
400-3-50 342 460 15.7 80 1.4 21.0 25
AKS009
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
220-3-50 198 253 39.7 198 1.4 52.7 70
400-3-50 342 460 19.9 99 1.4 26.3 35
AKS012
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
220-3-50 198 253 39.7 198 1.4 52.7 70
400-3-50 342 460 19.9 99 1.4 26.3 35
CSA
Canadian Standards Association
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code (U.S.A. Standard)
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
UL
Underwriters’ Laboratories
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
7
457