Terminal control
Bypass controller (33ZCBC-01) — The VVT bypass
controller is a component of Carrier’s 3V™ control system
and is used to regulate the supply duct static pressure for
Variable Volume and Temperature Applications. The
bypass Controller is an essential system component that
allows constant volume HVAC equipment to provide zone
level temperature control.
VVT zone controller (33ZCVVTZC-01) — The VVT
Zone Controller is a component of Carrier’s 3V control
system and is used to provide zone level temperature and
air quality control for Variable Volume and Temperature
Applications. The VVT zone controller is a pressure de-
pendent device that maintains space temperature by mod-
ulating the amount of supply airflow through its primary
damper. An integrated 35 in.-lb actuator is standard on all
VVT zone controllers.
VVT zone controllers are available factory mounted to
Carrier’s round and rectangular dampers. Round dampers
are available in 6, 8, 10, 12, 14, and 16-in. sizes. Rectan-
gular dampers are available in 8x10, 8x14, 8x18, and
8x24-in. sizes. All damper assemblies are equipped with an
integrated duct temperature sensor.
Zone controllers are available for field retrofit applications.
VAV zone controller (33ZCVAVTRM, 33ZCFANTRM) —
Carrier’s 3V control system provides seamless integration
of pressure independent zones for use with VVT systems.
Simply use Carrier’s family of VAV zone controllers
(ComfortID™) to regulate the flow of conditioned air into
the space. The VAV zone controllers provide dedicated
control functions for single duct terminals with modulating
heat (up to 2-stages of heat), series fan or parallel fan pow-
ered terminals, or as a primary controller for dual duct or
zone pressurization applications. Refer to Carrier’s Com-
fortID literature for additional information.
Linkage compatible unit controls and auxiliary
controls
Carrier’s 3V control system provides optimized equipment
control through airside linkage. Linkage allows the air
source to adjust its supply air temperature set points and
occupancy schedules to run in the most efficient manner.
The 3V control system linkage compatible controllers
include ComfortLink™, PremierLink™ and the Universal
Controller.
ComfortLink™ controls — The factory-integrated con-
trols are available on Carrier’s 2 to 25 ton Centurion
rooftop product line. The ComfortLink controller is a
component of Carrier’s 3V system and provides: optimum
performance of the rooftop’s refrigeration circuits, an
easy to read English scrolling marquee display and user
interface, and unparalleled diagnostic information with
factory-mounted sensors.
PremierLink™ control (33CSPREMLK) — The
PremierLink communicating controller is available as a fac-
tory-installed option on 3 to 25 ton rooftop units and as a
field-installed accessory. The control is DCV (Demand
Controlled Ventilation) compatible and internet ready.
Universal controller (33UNIVCTRL-01) The Uni-
versal Controller provides auxiliary building control to
interface with lighting, fans, pumps and other HVAC
equipment in a stand-alone or Carrier-networked environ-
ment using closed-loop, direct digital controls. The Univer-
sal Controller’s pre-engineered algorithms provide simple
building integration for small-to-medium commercial
applications with 16 field point capability (8 inputs and
8 outputs).
Interface devices
System Pilot (33PILOT-01) — The System Pilot is a
component of Carrier’s 3V control system and serves as
the user-interface and configuration tool for all Carrier
communicating devices. The System Pilot can be used to
install and commission a 3V zoning system, linkage com-
patible air source, universal controller and all other devices
operating on the Carrier communicating network.
ComfortVIEW™ software (CEPL130548-01) —
ComfortVIEW software can be installed on a PC and is
used to configure and monitor the 3V system.
Remote monitoring capability device
(33CSCCNWEB-01) — The remote monitoring device
installs on the Carrier network and provides a connection
for a phone line or ethernet connection, allowing the user
to view and change information using a standard web
browser. The user will also have access to the point dis-
plays, set point schedules, and operating schedules.
Field-installed accessories
Option board (33ZCOPTBRD-01) — Carrier’s option-
al relay board may be used with VVT zone controllers to
provide control functions for heat and fan air terminals.
Heating capabilities include modulating heat, up to 3 stag-
es of ducted heat or combination baseboard and ducted
heat control.
Mounting kit — Mounting kits are used to field install the
VVT zone controllers onto Carrier 33CS dampers. Mount-
ing kits come in packages of 10. The 33ZCMBRC-01 kit is
used when mounting on rectangular dampers. The
33ZCMBRD-01 kit is used when mounting on round
dampers.
Sensors
Outdoor-air sensor (HH79NZ039) — The outdoor-air
sensor reads temperatures between 0° and 150 F and is
used to report the outdoor-air temperature to the commu-
nication bus. The information can be used to lock out heat-
ing or cooling modes when the temperature is not within
user-configured limits. The outdoor-air sensor is needed
when an economizer is used.
Supply air temperature sensor (33ZCSENSAT) —
The supply air temperature sensor is required for heating
applications or stand-alone operation. The sensor has an
operating range of –40 to 245 F (–40 to 118 C) and in-
cludes a 6-in. stainless steel probe and cable.
Duct temperature sensor (33ZCSENDAT) — The
duct temperature sensor is required for use with a bypass
controller and must be installed in the supply air duct.
VVT® system key components